EQUIPMENT INSTALLATION continued
Valve Layout
Outlet 1" NPT
Meter
Cable
Drain 1/2" NPT
Figure 8
Water Line Connection
A bypass valve system is included and will be installed on all
water conditioning systems. Bypass valves isolate the softener
from the water system and allow unconditioned water to be
used. Service or routine maintenance procedures may also
require that the system is bypassed.
IMPORTANT: The bypass valve is shipped to you in the
bypass position (Figure 9 Series 360 Bypass Operation).
When the valve is in bypass water will not enter the
softening tank. The water in the building will not be
treated. Figure 9 Series 360 Bypass Operation, shows the
handles in the service position.
Once you have selected your location check the direction of
the waterflow in the main pipe. Figure 9 Series 360 Bypass
Operation can be used to plan the new plumbing assembly.
Inspect the main water pipe. Write down the type of pipe
(copper, plastic, galvanized etc.). Record the size of the pipe.
Plastic style pipes usually have the size printed on the outside.
Other pipes can be measured for the outside diameter and
converted into the pipe size at the store. Do not use pipe that is
smaller than the main water pipe .
The bypass requires two connector fittings that connect to the
plumbing. Size will be determined by the specific installation
requirements .
If the main plumbing is galvanized pipe and you are installing
copper pipe, then you must use dielectric insulating connectors
between the two styles of pipe.
Place the tank in position. The design of the tank does not
allow for bad alignment of the connections. You may ask your
supply store about flexable connections.
Take measurements and create a drawing of your installation.
Include pipe lengths and elbows that are needed . If the water
flow is from right to left you will need to cross the plumbing to
the softener. Take the drawing to your plumbing supply store.
Consult with their expert for installation ideas and suggestions .
Assemble the plumbing .
WARNING:
If pipes will be sweat soldered, do not
connect adapters to the bypass until the
pipes have cooled.
Inlet 1" NPT
To Brine Tank
3/8" NPT
Drain
Line
Connector
Assembly
"H" Clip
IN
OUT
Handles in Service
Figure 9 Series 360 Bypass Operation
WARNING:
The inlet water must be connected to the
inlet port of the valve. When replacing
an exsisting system, it is possible that
the inlet and outlet plumbing is installed
in a reverse position. Be certain the inlet
connection on the valve is connected to the
incoming water fitting from the water supply.
WARNING:
Do not use petroleum grease on gaskets
when connecting bypass plumbing. Use
only 100% silicone grease products when
installing any plastic valve. Non-silicone
grease may cause plastic components to fail
over time.
The bypass assembly connects to the water system by means
of a connector assembly. The connector is secured to the
plumbing and then inserted into the bypass. A clip is used to
hold it in place .
Figure 10 Connector Assembly
Before inserting the connector:
• Check that all O-rings are in place and not damaged.
• Lubricate O-rings and sliding surfaces with 100% silicone .
Firmly insert connector into bypass. Press locking clip into
position. Make certain the clip is fully engaged.
OM26KCS, OM32KCS, OM36KCS DE11 • 7
IN
OUT
Handles in Bypass