Installation Pre-Requisites; Installation - Leviton LumaCAN NPRPT-002 Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

NOTE: To be installed per all appropriate codes per your jurisdiction.
NOTE: For indoor use only.
1. Determine from where repeater will get power, choices are:
• Dedicated power supply (Use Leviton #A0015-000 or equivalent). Power
supply must be a Listed Class 2 power supply or Listed ITE power supply
marked LPS.
• Any LumaCAN
with enough capacity to power repeater).
2. Determine mounting location:
• 6-Port should be mounted in a 19" EIA rack mount enclosure, or may be
used in a desktop configuration.
• 2-Port may be surface mounted or installed into a field box.
3. Determine where LumaCAN
NOTE: Each end of the network must be terminated. Any mid-point device
must not be terminated. Any other configuration and the network will not
work reliably.
• 2-Port: Both ports are internally terminated and this can not be changed.
• 6-Port: Ports B-F are internally terminated and this can not be changed.
Port A has a termination switch and should be terminated when end-of-run.
4. Network/Power Wiring:
• All wiring is Class 2.
• When architecting the low voltage power system, refer to the "LumaCAN
power considerations white paper" (available at Leviton.com) which
identifies best practices and things to avoid. Additionally, ensure that there
is never multiple power-supplies powering the same segment.
• Do not connect to Ethernet networks. Although LumaCAN
connectors, it is not Ethernet and may cause damage to Ethernet systems.
5. Review system requirements from Leviton provided documents or as deduced
from field requirements.
1. Set Jumper positions.
• Refer to diagrams within this document for function.
2. Install device in the enclosure.
• 6-Port rack mount: The device will require one "long" and one "short"
rack mount ear.
NOTE: two devices also may be installed side by side by removing the
top cover, screwing the two devices together using the (2) provided holes,
reinstalling cover, then using only the short rack mounting ears.
• 6-Port desktop: Install provided rubber feet.
• 2-Port: Device may be installed as required by field conditions and allowed
by the authority having jurisdiction. Device is commonly installed "free air",
or in a steel box of appropriate size provided by the contractor.
3. Connect LumaCAN
• Reference LumaCAN
4. Connect power wires.

INSTALLATION PRE-REQUISITES

network Port (requires existing LumaCAN
TM
networks will be terminated:
TM

INSTALLATION

wires.
TM
wiring details for more information.
TM
Page 7
power supply
TM
uses RJ-45
TM