baltur TBL 85P Manual De Instrucciones De Uso página 9

Quemadores de gas de dos etapas
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

PIPES FOR LIGHT OIL BURNERS MODEL TBL 85P/ P DACA - 105P/ P DACA
DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
PUMP AXIS
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
PUMP AXIS
SUCTION - TYPE FEEDING SYSTEM
PUMP AXIS
N.B. For any missing devices in the piping, follow existing regulations.
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift.
0006081325_201409
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
H
meters
1
1,5
2
2,5
3
8 Automatic fuel interception
device at burner shut off
9 One-way valve
10 Bottom valve
H
meters
1
1,5
2
2,5
3
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
For each bend or valve deduct 0,25 m.
7 / 30
Total meters
meters
Ø i. 14 mm.
30
35
35
40
40
Total meters
meters
Ø i. 14 mm.
30
35
35
40
40
P = 3,5 m. (max.)
Total meters
H
meters
me-
Ø i. 14
Ø i. 16
ters
mm.
mm.
0,5
26
45
1
22
38
1,5
19
31
2
14
25
2,5
11
19