FM / CSA Installation Drawing
See Installation notes.
Terminal
41-44 and 51-54
Vt or Uo
5.71 V
It or Io
8.4 mA
Pt or Po
12 mW
Ca or Co
40µF
La or Lo
200 mH
Terminal
IS, Class I, Division 1, Group A,B,C,D
11-12 21-
22
T1..T5
Ta ≤
+60°C
T6
Ta ≤
+60°C
Vmax or Ui
30 V
Imax or Ii
120 mA
Pmax or Pi
0.84 W
Ci
2 nF
Li
1 µH
6350QE02revAB.doc 2004-02-06
18
Installation Drawing 6350QE02
Non Hazardous Location
Associated Apparatus
Barrier or FISCO Supply
With entity Parameters
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be
connected to any
associated apparatus that
uses or generates more
than 250V
Terminal
13,14 and 23,24
Vmax or Ui
30 V
Imax or Ii
140 mA
Pmax or Pi
1 W
Ci
0
Li
0
Class I,Zone 0 AEx ia IIC
Entity,Fisco
Ta ≤
Ta ≤
+60°C
+60°C
Ta ≤
Ta ≤
+45°C
+45°C
30 V
17.5 V
300 mA
250 mA
1.3 W
2.0 W
2 nF
2 nF
1 µH
1 µH
6350V103-ES
Hazardous (Classified) Location
Class I, Division 1, Group A, B, C, D
Class I, Zone 0 and Zone 1 AEx ia IIC
Class I, Division 2, Groups A, B, C, D
Po < Pi
Class I, Division 2, Group A,B,C,D
Class I, Zone 1 AEx ib IIC
Ta ≤
Ta ≤ +60°C
+60°C
Ta ≤
Ta ≤ +60°C
+45°C
15 V
30 V
any
250 mA
any
5.32 W
2 nF
2 nF
1 µH
1 µH
Rev. AB
CH1
14
41
13
42
12
43
11
44
CH2
21
51
22
52
23
53
54
24
6350B
CH1
14
41
13
42
12
43
11
44
CH2
21
51
22
52
23
53
54
24
6350B
CH1
14
41
13
42
12
43
11
44
CH2
21
51
22
52
23
53
54
24
6350B
Approved
Termination
Ta ≤ +60°C
Ta ≤ +60°C
17.5 V
any
any
2 nF
1 µH
1/7