5. PROGRAMMATION
5.2 Programmation avancée
IL EST UTILISÉ POUR RÉGLER LE
COURANT MAXIMAL
DE SURCHARGE DU MOTEUR
RANGE 0.5 ÷ 18.0A (SA604.xx)
RANGE 0.5 ÷ 90.0A (SA607.xx)
COURANT MAXIMAL
MAN. 16.5A
MAN. INDIQUE QUE
LA VALEUR DU COURANT
MAXIMAL A ÉTÉ
DÉFINIE MANUELLEMENT
COURANT MAXIMAL
AUT.
16.5 A
AUT. INDIQUE QUE LA VALEUR DU
COURANT MAXIMAL A ÉTÉ DÉFINIE
AVEC L'AUTO-APPRENTISSAGE
IL EST UTILISÉ POUR RÉGLER
LE DÉLAI D'INTERVENTION POUR LA
PROTECTION SUR LE COURANT
RANGE 1 ÷ 8s
DELAI COURANT
4 s
DELAI COURANT
4 s
IL EST UTILISÉ POUR RÉGLER
LE COURANT MINIMAL
DU MOTEUR
RANGE 0.5 ÷ 15.0A (SA604.xx)
RANGE 0.5 ÷ 87.0A (SA607.xx)
COURANT MINIMAL
OFF
OFF. EXCLUT LE
CONTRÔLE SUR
LE COURANT MINIMAL
COURANT MINIMAL
AUT.
9.9 A
COURANT MINIMAL
AUT.
9.9 A
AUT. INDIQUE QUE LA VALEUR DU
COURANT MINIMAL A ÉTÉ DÉFINIE
AVEC L'AUTO-APPRENTISSAGE
STABLE DÉMARRE LE MOTEUR AVEC
UN PULSE SUR LE BOUTON MAN;
ARRÊTE LE MOTEUR AVEC UN
PULSE SUR LE BOUTON RESET
BOUTON MANUEL
STABLE
INSTABLE DÉMARRE LE MOTEUR
SEULEMENT PENDANT LA
PRESSION SUR LE BOUTON MAN
BOUTON MANUEL
INSTABLE
BOUTON MANUEL
INSTABLE
10
IL EST UTILISÉ POUR RÉGLER
LE DÉSÉQUILIBRE DU
COURANT SUR LES PHASES
RANGE: OFF - 5% - 10% - 15%
DESEQUILIBRE DES
PHASES OFF
OFF EXCLUT LE
DÉSÉQUILIBRE DES
PHASES
DESEQUILIBRE DES
PHASES 10%
DESEQUILIBRE DES
PHASES 10%
IL EST UTILISÉ POUR RÉGLER
L'ATTENTE PRÉSENCE RÉSEAU
RANGE 1 ÷ 30min
ATTENTE PRESENCE
RESEAU 1min.
ATTENTE PRESENCE
RESEAU OFF
OFF EXCLUT L'ATTENTE
PRÉSENCE RÉSEAU
ATTENTE PRESENCE
RESEAU OFF