Temperature warning
The unit will automatically report if the temperature will exceed the set value. The default setting for low temperature alarm is
+5°C and for high temperature 30°. These values can be changed to between 0°C and +50°C. To change a set value, send the
following text message to the unit:

LOW TEMPERATURE ALARM

LTWARN <NUMBER>
The example above will cause the unit to send a warning
report when the temperature falls below 12°C, as
"Temperature - LOW".
If the temperature then increases again and reaches
the set value, another message will be sent saying:
"Temperature - RESTORED"
The unit's temperature warning function can be easily
activated or deactivated using the following command:
Activation:
LTWON
Deactivation: LTWOFF
Request current temperature
To see what the current temperature is where your ControlBox24/7 is located, send the following text message to the unit:
TEMP
Example: LTWARN 12
(default setting)

HIGH TEMPERATURE ALARM

HTWARN <NUMBER>
The example above will cause the unit to send a
warning report when the temperature exceeds 27°C as
"Temperature - HIGH".
If the temperature then decreases again and reaches
the set value, another message will be sent saying:
"Temperature - RESTORED"
The unit's temperate warning function can be easily
activated or deactivated using the following command:
Activation:
HTWON
Deactivation: HTWOFF
9
PROGRAMMING
Example: HTWARN 27
(default setting)