Remote
Card
Description
Control
Transparent Parameters
13
P13
No function (P02=1)
Hot water tank activation hysteresis
temperature
(P02=2)
No function (P02=3)
No function (P02=4)
No function (P02=5)
Hot water tank activation hysteresis
temperature
(P02=6)
14
P14
No function (P02=1)
Hot water tank preparation delivery
temperature (P02=2)
Hot water tank preparation delivery
temperature (P02=3)
Delivery temperature adjustment in
DHW mode (P02=4)
Delivery temperature adjustment in
DHW mode (P02=5)
Hot water tank preparation delivery
temperature (P02=6)
15
P15
Boiler shell Warm-up activation tem-
perature (P02=1)
Boiler shell Warm-up activation tem-
perature (P02=2)
Boiler shell Warm-up activation tem-
perature (P02=3)
Comfort activation temperature
(P02=4)
Comfort activation temperature
(P02=5)
Boiler shell Warm-up activation tem-
perature (P02=6)
16
P16
Boiler shell Warm-up deactivation
hysteresis (P02=1)
Boiler shell Warm-up deactivation
hysteresis (P02=2)
Boiler shell Warm-up deactivation
hysteresis (P02=3)
Comfort deactivation hysteresis
(P02=4)
Comfort deactivation hysteresis
(P02=5)
Boiler shell Warm-up deactivation
hysteresis (P02=6)
17
P17
System min. pressure value
18
P18
System nominal pressure value
19
P19
No function (P02=1)
Legionella protection (P02=2)
No function (P02=3)
No function (P02=4)
No function (P02=5)
Legionella protection (P02=6)
20
P20
Mains Voltage Frequency
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"In" - Information Menu
The card can display the following information:
t1
NTC Heating sensor (°C)
t2
NTC DHW sensor (°C)
(Only with Parameter P02=2, boiler with storage or with Parameter P02=6,
boiler with storage)
t3
NTC Safety sensor (°C)
t4
NTC External sensor (°C)
P5 Actual system water pressure (bar/10)
Press the Heating buttons to scroll the list of information. In case of damaged sensor, the
card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
14
EN
Range
Default
--
--
0-20°C
40°C
--
--
--
--
--
--
0-20°C
40°C
--
--
70-85°C
80
70-85°C
80
50-65°C
55
50-65°C
55
70-85°C
80
0-80°C
0°C
0-80°C
0°C
0-80°C
0°C
0-80°C
55°C
0-80°C
55°C
0-80°C
0°C
0-20°C
5°C
0-20°C
5°C
0-20°C
5°C
0-20°C
20°C
0-20°C
20°C
0-20°C
5°C
0-8 bar/10
2 bar/10
5-20 bar/10
6 bar/10
--
--
0-7
0
--
--
--
--
--
--
0-7
0
0=50Hz,1=60Hz
0=50Hz
between 05 and 125°C
between 05 and 125°C
between 05 and 125°C
between -30 and 70°C
(Negative values flash)
00-99 bar/10
cod. 3540Z230 - 01/2011 (Rev. 00)
"Hi" - History Menu
The microprocessor can memorise the total hours with card fed (Ht), the last 10 faults
(with detail of the time they occurred, referring to parameter Ht) and hours of burner op-
eration (Hb).
The History datum item H1 represents the most recent fault that occurred, whereas the
History datum item H10 represents the least recent. The codes of the faults saved are
also displayed in the corresponding menu of the Opentherm remote temperature control
Note for calculation of hours:
Every 24 hours, the number shown in the part of the display normally reserved for
system pressure is increased by one unit.
Every hour, the number shown in the part of the display normally reserved for room
temperature is increased by one unit.
Press the Heating buttons to scroll the list of faults.
Ht
Total hours with card fed.
H1
Fault code --> The time when the fault occurred (referring to Ht)
H2
Fault code --> The time when the fault occurred (referring to Ht)
H3
Fault code --> The time when the fault occurred (referring to Ht)
H4
Fault code --> The time when the fault occurred (referring to Ht)
H5
Fault code --> The time when the fault occurred (referring to Ht)
H6
Fault code --> The time when the fault occurred (referring to Ht)
H7
Fault code --> The time when the fault occurred (referring to Ht)
H8
Fault code --> The time when the fault occurred (referring to Ht)
H9
Fault code --> The time when the fault occurred (referring to Ht)
H10
Fault code --> The time when the fault occurred (referring to Ht)
Hb
Hours of burner operation.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"rE" - History Reset
Press the Eco/comfort button for 3 seconds to delete all the faults and times stored in the
History Menu: the card will automatically exit the Service Menu, in order to confirm the
operation.
Press the Reset button to return to the Service Menu.
4.2 Start-up
B
Checks to be made at first lighting, and after all maintenance operations that
involved disconnecting from the systems or an intervention on safety devices
or parts of the boiler:
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the seal of the fuel system.
Check correct prefilling of the expansion tank.
Fill the water system and make sure that all air contained in the boiler and the sys-
tem has been vented, by opening the air valve on the boiler and any air valves on
the system.
Make sure there are no water leaks in the system, domestic hot water circuits, con-
nections or boiler.
Check correct connection of the electrical system and efficiency of the earthing sys-
tem
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
Checks during operation
Turn the unit on as described in sec. 2.3.
Check the seal of the fuel circuit and water systems.
Check the efficiency of the flue and air-fume ducts during boiler operation.
Make sure the water is circulating properly between the boiler and systems.
Check correct boiler lighting by performing various tests, turning it on and off with
the room thermostat or remote control.
Make sure the fuel consumption indicated on the meter matches that given in the
technical data table on sec. 5.3.
Ensure the seal of the fumebox and burner door.
Make sure the burner works properly. This check must be made with the special in-
struments, following the manufacturer's instructions.
Check correct programming of the parameters and carry out any required customi-
sation (compensation curve, power, temperatures, etc.).