INSTALLATOR SET
Condensation regulation setting corresponding to the external
Cond.low
temperature T.C.low
Condensation regulation differential setting corresponding to the
Diff.low
external temperature T.C.low
Condensation regulation setting corresponding to the external
Cond.hig
temperature T.C.high
Condensation regulation differential setting corresponding to the
Diff.hig
external temperature T.C.high
Cond. PC
Corresponding condensation regulation setting in the heat pump
Diff. PC
Condensation regulation differential corresponding to the heat pump
Low outside temperature limit for the selection of the setting and
T.C.low
selection differential
High outside temperature limit for the selection of the setting and
T.C.high
selection differential
Volt Min
Minimum DCP output voltage when cold
High pressure value below which DCP output is 0 volts during low
DcpR Off
temperature pre-ventilation.
High pressure value above which DCP output is 10 volts during
DcpR On
low temperature pre-ventilation
S. R Heating
Thermostat setting to manage the water inlet recovery.
Setting to determine the distance between one step and the
D.Tot.R
following one, in the recovery operation setting.
Temperature (read by the probe on the fluid) above which the
T. OutS.
DEFROSTING action can END
Number of
Number of supplementary heaters (number of steps).
resistors
Set Res
External air setting under which electrical elements are enabled
% power of each supplementary heater step compared with the
Power Res
machine 100 % value
Setting in comparison with the external air. Below this value,
Set Ta CP
compressors will be disabled if P.C. supplementary heaters are
present.
Numb. of pumps
Total number of evaporator pumps
Numb. of pumps
No. of pumps switched on at the same time.
ON
In/Out H20
Temperature regulation selection on the water inlet/outlet
Integration time (integral error calculation) for regulation in water
Time Int
outlet.
Compressor override mask if the power limit control is active:
CP1-CP2B
CP1-CP2-CP1A-CP2A-CP1B-CP2B
V.max FC
Maximum DCP voltage in freecooling
Enabling of the pump powering up as antifreeze protection together
AG pump
with the evaporator electrical elements.
Enabling at the multichiller control (network control of more than
MultiTRIO
one chiller with master and slaves)
Language
Language selections used: Italian, English, German, and French
Description
Default value
17 bar
20 bar
17 bar
12 bar
45 bar
5 bar
-5 °C
40°C
1V
22 bar
23 bar
50°C
5°C
20°C
0
5°C
0
-5 °C
0
0
IN
600
111111
10V
OFF
OFF
- - -
15