®
IntesisBox
KNX - Daikin A.A. (Gama SKY & VRV)
Apéndice A – Tabla de Objetos de Comunicación
NÚMERO
SECCIÓN
DE
OBJETO
On/Off
0
Control_ On/Off
1
Control_ Modo
2
Control_ Modo Frío/Calor
3
Control_ Modo Frío & On
4
Control_ Modo Calor & On
5
Control_ Modo Auto
Modo
6
Control_ Modo Calor
7
Control_ Modo Frío
8
Control_ Modo Ventilador
9
Control_ Modo Seco
Control_ Modo +/-
10
Control_ Modo +/-
Control_ Vel. Vent. / 2 Vel.
Velocidad
11
Control_ Vel. Vent. / 3 Vel.
del Ventilador
Control_ Vel. Vent. / 2 Vel.
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
NOMBRE
LONG.
1 bit
1 byte
DPT_HVACContrMode
1 bit
DPT_Heat/Cool
1 byte
1 byte
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 byte
1 byte
1 byte
DPT_Enumerated
TIPO DE DATAPOINT
FLAGS
DPT_NAME
DPT_ID R
W
DPT_Switch
1.001
W
20.105
W
1.100
W
DPT_Scaling
5.001
W
DPT_Scaling
5.001
W
DPT_Bool
1.002
W
DPT_Bool
1.002
W
DPT_Bool
1.002
W
DPT_Bool
1.002
W
DPT_Bool
1.002
W
DPT_Step
1.007
W
DPT_UpDown
1.008
W
DPT_Scaling
5.001
W
DPT_Scaling
5.001
W
5.010
W
URL
Email
tel
Manual de usuario r8.1 esp
FUNCIÓN
T U
T
0 - Off; 1-On
T
0 - Auto; 1 - Calor; 3 - Frío; 9 – Vent.; 14 – Seco
T
0 - Frío; 1 - Calor
T
0% - Off; 0.1%-100% - On + Frío
T
0% - Off; 0.1%-100% - On + Calor
T
1 – Auto
T
1 – Calor
T
1 – Frío
T
1 – Ventilador
T
1 – Seco
0 - Decrementar; 1 – Incrementar
0 - Arriba; 1 - Abajo
T
0%-74% - Vel. 1; 75%-100% - Vel. 2
0%-49% - Vel. 1; 50%-83% - Vel. 2;
T
84%-100% Vel. 3
T
1 – Vel. 1; 2 – Vel. 2
http://www.intesis.com
info@intesis.com
+34 938047134
51 / 56