IntesisBox
KNX - Daikin A.A. (Gama SKY & VRV)
Control_ Temp Consigna +/-
26
Control_ Temp Consigna +/-
Control_ Contacto de Ventana
27
Control_ Contacto de Ventana
Temporizador
28
Control_ Presencia
29
Control_ Temporizador Sleep
30
Control_ Bloqueo Control Remoto
Bloqueo
31
Control_ Bloqueo Objetos Control
32
Control_ Modo Power
Modos
33
Control_ Modo Econo
Especiales
34
Control_ Modo Calor Adicional
35
Control_ Modo Frío Adicional
36
Control_ Guardar/Ejec Escena
37
Control_ Guardar Escena 1
38
Control_ Guardar Escena 2
Escenas
39
Control_ Guardar Escena 3
40
Control_ Guardar Escena 4
41
Control_ Guardar Escena 5
42
Control_ Ejecutar Escena 1
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
1 bit
DPT_Step
1.007
1 bit
DPT_UpDown
1.008
1 bit
DPT_OpenClose
1.009
1 bit
DPT_Start
1.010
1 bit
DPT_Occupancy
1.018
1 bit
DPT_Start
1.010
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Start
1.010
1 bit
DPT_Start
1.010
1 bit
DPT_Start
1.010
1 bit
DPT_Start
1.010
1 byte
DPT_SceneControl
18.001
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
Manual de usuario r8.1 esp
W
0 - Decrementar; 1 – Incrementar
W
0 - Arriba; 1 - Abajo
W
T
0 - Abierto; 1 - Cerrado
W
T
0 - Parar; 1 – Arrancar
W
T
0 – No ocupado; 1 - Ocupado
W
T
0 - Parar; 1 – Arrancar
W
T
0 - Desbloqueado; 1 - Bloqueado
W
T
0 - Desbloqueado; 1 - Bloqueado
W
T
0 - Parar; 1 – Arrancar
W
T
0 - Parar; 1 – Arrancar
W
T
0 - Parar; 1 – Arrancar
W
T
0 - Parar; 1 – Arrancar
0 a 4 – Ejec. Escene de 1 a 5;
W
128 to 132 – Guardar Escena de 1 a 5
W
1 – Guardar Escena
W
1 - Guardar Escena
W
1 - Guardar Escena
W
1 - Guardar Escena
W
1 - Guardar Escena
W
1 – Ejecutar Escena
URL
http://www.intesis.com
Email
info@intesis.com
tel
+34 938047134
53 / 56