7. Códigos de Error
Error code KNX
RC Display
object
65535 (-1 if
-
signed)
F15
1501
F16
1601
F17
1701
2001
F20
2010
F21
2101
F26
2601
2701
2701
F27
2701
2701
3001
F30
3001
3101
F31
3101
3101
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
Location or problem
Error in the communication of PA-AC-KNX-1i
device with the AC unit
Drain level Float switch problem
Louver switch problem
D.C. Fan motor problem
Indoor temperature sensor problem
Remote control thermistor problem
Pipe temp. sensor problem
(indoor unit)
Remote control transmission
problem
Indoor/outdoor unit disconnection problem
Indoor/outdoor
unit
connection
problem
Indoor/outdoor unit disconnection problem
Indoor/outdoor
unit
connection
problem
System problem
Open phase, or reversed phase of supply
Suction pressure protection
High-pressure cut-off
4 way valve problem
Manual de usuario r1 esp
Check location
Indoor/gateway connection wire
Drain pump and drain pipe, indoor unit
connectors
Louver motor, decorative panel connection
terminal, or indoor unit louver motor connectors
Indoor unit D.C.Fan motor or connection
terminals
Indoor temperature sensor lead wire or indoor
unit connector
Remote control thermistor
Pipe temperature sensor lead wire or indoor unit
connector
Remote control unit cable and connection
terminals
Indoor/outdoor
unit
connection terminals, or indoor unit power
supplies (indoor side)
error
Indoor/outdoor unit connection wire (indoor side)
Indoor/outdoor
unit
connection terminals, or outdoor unit power
supplies (outdoor side)
error
Indoor/outdoor unit connection wire (outdoor
side)
Total capacity for the number of indoor units is
insufficient, or over. Check the total capacity and
the number of indoor units
Check the main power supply terminal board
connections, or switch over any two of the
power supply wires.
Insufficient
refrigerant
(closed)
Check the Refrigeration system
Check the 4 way valve or lead wire
URL
http://www.intesis.com
Email
info@intesis.com
tel
+34 938047134
connection
cable
and
connection
cable
and
or
valve
operation
54 / 62