Technical Data - Victron energy Phoenix Inverter Smart 12/1600 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

7. Technical data

Phoenix Inverter Smart
Parallel and 3-phase operation
Input voltage range (1)
Output
Cont. output power at 25ºC (2)
Cont. output power at 25ºC
Cont. output power at 40ºC
Cont. output power at 65ºC
Peak power
Dynamic (load dependent) DC low shut down
(fully configurable)
Max. efficiency 12/ 24 /48 V
Zero load power 12 / 24 / 48 V
Zero load power in ECO mode
Programmable relay (2)
Stop & start power ECO-mode
Protection (3)
Bluetooth wireless communication
VE.Direct communication port
Remote on-off
Common Characteristics
Common Characteristics
Battery-connection
230 V AC-connection
Weight
Dimensions (hxwhd)
Safety
Emission Immunity
Automotive Directive
1) Non-linear load, crest factor 3:1
2) Programmable relay that can a.o. be set for general
alarm, DC under voltage or genset start/stop function.
AC rating: 230 V / 3 A
DC rating: 3 A up to 30 VDC, 0.2A up to 70 VDC
14
12 Volt
12/1600
24 Volt
24/1600
48 Volt
48/1600
INVERTER
Output voltage: 230VAC ±2%
1600VA
1300W
1200W
800W
3000VA
https://www.victronenergy.com/live/ve.direct:phoenix-inverters-
92/94/94 %
8/9/11 W
0,6/1,3/2,1 W
GENERAL
Operating temperature range: -40 to +65ºC (fan assisted cooling)
ENCLOSURE
Material & Colour: steel (blue RAL 5012; and black RAL 9017)
M8 bolts
12kg
485 x 219 x 125mm
STANDARDS
3) Protection key:
12/2000
24/2000
48/2000
No
9,3 – 17V
18,6 – 34V
2000VA
1600W
1450W
1000W
4000VA
Dynamic cut-off, see
dynamic-cutoff
92/94/94 %
8/9/11 W
0,6/1,3/2,1 W
Yes
adjustable
a - g
For remote monitoring and system integration
For remote monitoring and system integration
Yes
Humidity (non-condensing): max 95%
Protection category: IP 21
M8 bolts
Screw terminals
13kg
485 x 219 x 125mm
EN-IEC 60335-1
EN 55014-1 / EN 55014-2 / EN-IEC 61000-6-1
EN-IEC 61000-6-2 / EN-IEC 61000-6-3
ECE R10-5
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 V AC on inverter output
g) input voltage ripple too high
12/3000
24/3000
48/3000
37,2 – 68V
50 Hz or 60Hz ± 0,1% (1)
3000VA
2400W
2200W
1700W
6000VA
93/94/95%
12/13/15 W
1,5/1,9/2,8 W
2+2 M8 bolts
19kg
533x285x150mm (12V)
485x285x150mm (24/28V)

Publicidad

Tabla de contenido
loading

Tabla de contenido