• In the event of mains absent or incorrect (off margins) the inverter supplies pseudo-sinusoidal wave energy from the
batteries for a limited time.
• When the mains returns or finds its corresponding margins, the charge is supplied once more from the commercial mains
after filtering, and also through the stabiliser.
• Additionally, it has protection against tension tips to the telephone line (Fax, Modem...), through connectors RJ-
11/RJ-45.
• The mere fact of the unit being connected to the mains means that the batteries are recharged.
• If the SPS is overloaded in any of its working modes and the load connected to the output is not reduced, the unit will
stop supplying output voltage in a few seconds:
Line Mode
110%+20%/-10%; shutdown after 5 minutes and pass to fault mode.
120%+20%/-10%; shutdown immediate and passo to fault mode.
Battery Mode
110%+20%/-10%; shutdown aflter 5 seconds.
120%+20%/-10%; shutdown immediate.
• The unit has automatic detection of the input frequency, which is activated when it is connected to the mainssupply.
• The SPS provides with a software of supervision «Winpower Administrator» and a cable of connection in order to use
between the equipment and its computer . With it an intelligent operation is obtained, that provides a perfect protection
of the loads.