Switching mode power supplies IO-Link ready
BAE PS-XA-1S-24-200-104
Technical data
Values measured at +25°C and full load
Electrical data
Input/output insulation voltage
Insulation resistance
Turn-on time
Switching frequency f
Interconnected operation type
Parallel connection
Series connection
Settling time
Temperature coefficient
Ripple & Noise
Holdup time
at 230 V AC
at 115 V AC
Power boost
Efficiency
Short circuit response
Alarm contacts
Overvoltage category
Input data
Rated input voltage
Input voltage range
Rated input current
at 230 V AC
at 115 V AC
Inrush current
at 230 V AC
at 115 V AC
Frequency range
Input fuse
www.balluff.com
3 kV AC
> 100 MΩ
< 1 s
115 kHz (typ)
not allowed
max. 2 devices
2 ms
±0.03%/°C
50 mV
pp
(BW
= 20 MHz)
max.
> 30 ms
25 ms
150% for max. 4 s,
1 × per minute
> 94 % (typical)
Continuous operation
20 A, continuous
short circuit protected
DC Alarm, Lifetime,
Stress level
II (OVCII)
115/230 V AC
90...132 /
198...264 V AC
4.6 A
9 A
< 20 A
< 15 A
47...63 Hz
T 12 A internal, only to
be replaced by the
manufacturer
Output data
Rated output voltage
Rated output current
Output power
Setting range
Output accuracy
Voltage regulation
Load regulation
Load type
Mechanical data
Housing material
Weight
Dimensions W x H x D mm
Connections
Input
AWG
Output
AWG
Alarm
AWG
Terminal tightening torque
Pollution Degree
Mounting type
Indicators
Stress Level
Lifetime
Load Level
Environmental conditions
Operating temperature
Derating
Storage temperature
Relative air humidity
Cooling
Degree of protection per
IEC 60529
Output type
24 V DC
20 A
480 W
22...28 V DC
±1.0%
±0.5%
±0.5%
resistive/capacitive
Metal
1.1 kg
79 × 127 × 131
2 mm²...2.5 mm²
AWG14...AWG13
1 mm²...4 mm²
AWG17...AWG11
0.25 mm²...1.5 mm²
AWG24...AWG16
0.6...0.8 Nm
2
DIN-rail mounting
Green, yellow, red
LEDs
Green, yellow, red
LEDs
Green, yellow, red
LEDs
–25...+60°C
–3.5 %/°C
above +50°C
–25...+85°C
20...95 % non-
condensing
Free convection
IP20
SELV
english
7