7-2. Multiple unit installation

・When installing multiple units, make sure to take into consideration factors such as providing enough space for people to pass through, ample
space between blocks of units, and sufficient space for airflow. (The areas marked with Ⓐ in the figures below must be left open.)
・In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to
L1, L2, and L3 as shown in the tables below.
・If there are walls in the front and rear of the block of units, up to six units (three units for units P120 through P168) can be installed consecutively
side by side, and a space of 1000 mm (39-3/8 in) or more must be left between each block of six units.
(1) Side-by-side installation
When the distances between the units (L4) need to be small
L4
h1
Unit height
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4) + h1
300 (11-13/16) + h2
(2) Face-to-face installation
When there are walls in the front and rear of the block of units
h1
Unit height
L1
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4) + h1
100 (3-15/16) + h2
(3) Combination of face-to-face and side-by-side installations
When there are walls in the front and rear of the block of units
h2'
500 (19-11/16)
Required minimum distance [mm (in)]
L2 (Right)
300 (11-13/16) + h2
300 (11-13/16) + h2'
Leave open in two directions.
WT07598X02
h2
500 (19-11/16)
L2
L1
L2 (Rear)
L4 (Between)
30 (1-3/16)
h2
500 (19-11/16)
L2
L4
L4
L2 (Rear)
L4 (Between)
450 (17-3/4)
h2
500
(19-11/16)
L2
L4
L2'
L2' (Left)
L4 (Between)
900 (35-7/16)
When the distance behind the block of units (L2) needs to be small
L4
h1
Unit height
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4) + h1
100 (3-15/16) + h2
When there is a wall on either the right or left side of the block of units
h3
Unit height
L3
Required minimum distance [mm (in)]
L3 (Right/Left)
15 (5/8) + h3
When there are two walls in an L-shape
L3
Required minimum distance [mm (in)]
L2 (Right)
L3 (Right/Left)
300 (11-13/16) + h2
1000 (39-3/8) + h3
GB-13
h2
500 (19-11/16)
L2
L1
L2 (Rear)
L4 (Between)
100 (3-15/16)
L4
L4
L4 (Between)
450 (17-3/4)
h3
Unit height
500
(19-11/16)
L2
L4
L4 (Between)
900 (35-7/16)
h2