Cautions, Warnings and Instructions
Wiring Warnings for Electrical Practices and Wire Sizes
The Cautions, Warnings, and instructions in this section summarize the
procedures necessary to ensure a soft starter installation complies with
®
Underwriters Laboratories
guidelines.
NOTICE
UL/CSA = Cu only, Ampacity per 75 °C Table.
NOTICE
Open Type Equipment.
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are
presented in the table below.
Wire size
Power
Model Types
1x
AWG
DS7-340SX016N0-N
18 - 6
DS7-340SX024N0-N
DS7-340SX032N0-N
DS7-342SX016N0-N
18 - 6
DS7-342SX024N0-N
DS7-342SX032N0-N
Circuit Breaker and Fuse Sizes
The soft starter connections to input power must include UL Listed inverse time
circuit breakers with 600 V rating, or UL Listed fuses as shown in the table
below.
SC Ratings
Model Types
DS7-340SX016N0-N
5 KA, 480 V AC
DS7-342SX016N0-N
DS7-340SX024N0-N
5 KA, 480 V AC
DS7-342SX024N0-N
DS7-340SX032N0-N
5 KA, 480 V AC
DS7-342SX032N0-N
8/8
Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
© 2010 by Eaton Industries GmbH,
Eaton.eu/documentation
2x
2
2
mm
AWG
mm
0.75 - 16
18 - 6
0.75 - 3.5
0.75 - 16
18 - 6
0.75 - 3.5
Branch Circuit Protection
100 A RK5 fuse or breaker
100 A RK5 fuse or breaker
125 A RK5 fuse or breaker
Motor Overload Protection
NOTICE
Each motor must be protected against thermal overload.
Soft starter DS7 requires against thermal overload an combination with an
overload relay (PKZ, PKE) or a bimetallic relay (ZB).
If two or more motors are connected behind the soft starter, each engine must
be separately protected against thermal overload.
Control
1x
2x
2
AWG
mm
AWG
mm
18 - 14
0.5 - 2.5
18 - 16
0.5 - 1.0
18 - 14
0.5 - 2.5
18 - 16
0.5 - 1.0
AWG = American Wire Gauge. Smaller numbers represent increasing wire thickness.
MCM/kcmil = 1,000 circular mils, a measure of wire cross-sectional area
2
mm
= square millimeters, a measure of wire cross-sectional area
NOTICE
Suitable for use on a circuit capable of delivering not more than
5,000 rms symmetrical ampers, 480 V maximum.
Max. HP [V AC]
200
240
480
3
5
10
7.5
5
15
10
10
25
Emergency On Call Service: Local representative
USA: EatonCare at
Eaton.com/recycling
All Rights Reserved
Torque
Power
Control
2
Nm
lb-in
Nm
3.2
28.32
0.6
3.2
28.32
0.6
Max. kW [V AC]
230
400
4
7.5
5.5
11
7.5
15
Eaton.eu/aftersales
or +49 (0) 180 5 223822 (de, en)
Eaton.com/eatoncare
or 877-386-2273
13346985
lb-in
5.31
5.31
03/20 IL03902004Z