1 Intended use
This device fulfills the directive 2014/34/EC and is suited for use in
explosion hazardous areas according to EN 60079-0:2012 + A11 and EN
60079-11:2012.
Further it is suited for use in safety-related systems, including SIL2 as per
IEC 61508. In order to ensure correct operation to the intended purpose it is
required to observe the national regulations and directives.
2 Hazardous areas
II 2 G and II 1 D (Group II, Category 2 G, electrical equipment for gaseous
atmospheres and category 1 D, electrical equipment for dust atmospheres).
.
3 Marking
 II 2 G and Ex ia IIC T6 Gb acc. to EN60079-0 and -26 and
 II 1 D Ex ia IIIC T95 °C Da IP67 acc. to EN60079-0
4 Local admissible ambient temperature
-25...+70 °C
5 Installation/Commissioning
These devices may only be installed, connected and operated by trained and
qualified staff. Qualified staff must have knowledge of protection classes,
directives and regulations concerning electrical equipment designed for use
in explosion hazardous areas.
Please verify that the classification and the marking on the device comply
with the actual application conditions.
This device is only suited for connection to approved Exi circuits according
to EN 60079-0 and EN 60079-11. Please observe the maximum admissible
electrical values.
After connection to other circuits the sensor may no longer be used in Exi
installations. When interconnected to (associated) electrical equipment,
it is required to perform the "Proof of intrinsic safety" (EN60079-14).
Attention! When used in safety systems, all content of the security manual
must be observed.