RT70
Model
PE
Q1
Range
20-25A
Adjustment
23A
Q2
Range
20-25A
Adjustment
23A
Q3
Range
9-14A
Adjustment
11A
Q4
6A
Q7/8
Range
/
Adjustment
/
FT1
2A
FT3
10A
FT4
10A
Contactor AC3
KM1
25A
KM2
25A
KM3
12A
KM4
9A
KM7
9A
KM8
9A
COMPRESSORS CRANKCASE HEATER
Models
RT30
Power
W
70
PRESSOSTATS SETTING
Refrigerant circuit
Factory low pressure adjustment 2bars (29PSI)
Factory high pressure adjustment 42bars (609.16PSI)
Clogged filter DP warning (upstream/downstream filters) > 250 Pa
Airflow detector DP warning (upstream/downstream blower)< 50 Pa
RT80
GE
PE
GE
24-32A
31A
24-32A
31A
13-18A
15.5A
6A
/
/
2A
10A
10A
32A
32A
18A
9A
9A
9A
RT40
RT50
RT60
70
90
90
16
RT100
PE
GE
PE
25-40A
31A
25-40A
40A
13-18A
15.5A
6A
2.5-4A
2.5A
2A
/
/
40A
40A
18A
9A
6A
6A
RT70
RT80
RT100
90
75
90+75
RT110
GE
25-40A
40A
25-40A
40A
13-18A
15.5
6A
2.5-4A
2.5A
2A
/
/
40A
40A
18A
9A
6A
6A
RT110
75