Commissioning
4.3 Nominal heat load
26
Setting the nominal heat load
If none of the gas types given in the injector pressure table are available at the in-
stallation site, the nominal heat load is lower or higher. If an adapted nominal out-
put setting should be made deviating from the factory setting, the required set
value (gas flow in l/min) must be taken from the following table.
Model
Nominal heat load (full load)
Operating heating value
H
in kWh/m
uB
Gas valve CG 15 R03 VW5 WZ
kW
7,0
7,5
8,0
8,5
9,0
3
9,5
10,0
10,5
11,0
11,5
SGB 90 C/D
90,0
Gas flow in l/min
213
199
187
176
166
158
150
143
136
130
7313157-02 02.14