EN
How to connect the wiring to the terminal block
Pay attention during wiring operations.
carefully with a knife, etc.
(1) Use crimp terminals with isolating sleeves, as shown in the following
the cables do not loosen.
10 m m
30 m m
exert any pressure on the terminal blocks.
(4) Use a suitable screw driver to tighten the terminal block screws. Do not
use a damaged screw driver otherwise screw heads may be damaged
and screws improperly tightened.
(5) Do not overtighten the terminal block screws as this might result in
breakage of the screws.
Wire
Screw with special washer
Crimp-type terminal
Terminal blocks
Couple of tightening
Vite M3
da 0,3 a 0,6 N.m (3 a 6 kgf.cm)
Vite M4
da 1,2 a 1,8 N.m (12 a 18 kgf.cm)
Section II :: Installation and maintenance
Crimp-type terminal
Sleeve
Screw with special washer
Crimp-type terminal
Wire
94
ATTENTION
• Faulty wiring may cause not only a malfunction but also damage to the
TERMINAL BLOCK board.
• Tighten each screw enough.
• Pull gently on the wire to check its full insertion.
• The stripping of the connection cable coating should be 10 mm. If it is
shorter, there may be a defective contact.
If it is longer, there may be a short circuit.
tightening torques, otherwise it is possible that an abnormal overheating
is produced which could cause severe damage inside the unit.
• When connecting the power supply cable, make sure that the power
supply phase corresponds to the terminal block phase.
• To connect the power supply cable to the terminal block, it is necessary that
the current carrying conductors are taut before earthing the conductor,
otherwise the cable may slip out from its anchorage.