Idiomas disponibles

Full three-phase installation, without neutral
MAINS
DCRG8
L1 L2 L3 N
INPUT
CURRENT
VOLTAGE
100-415V~
1/5A~
100-600V~
1
4
7
2
3
5
6
8
I1 I2 I3 C
L1 L2 L3 N
S1
S1
CT1
S1
CT2
S2
CT3
FU9
QS1
FU13
LOAD
TC1
FULL THREE-PHASE CONNECTION, WITHOUT NEUTRAL
Wiring configuration used for standard applications with full three-phase voltage control
Voltage measurement
Current measurement
Phase angle offset
Capacitor overload measurement
Parameter setting
NOTE: Recommended fuses for aux supply and voltage measurement inputs: F1A (fast).
Full three-phase installation, with neutral
MAINS
DCRG8
L1 L2 L3 N
INPUT
CURRENT
VOLTAGE
100-415V~
1/5A~
100-600V~
110-250V=
1
2
3
4
5
6
7
8
I1 I2 I3 C
L1 L2 L3 N
S1
S1
CT1
S1
CT2
S2
CT3
FU9
QS1
FU13
LOAD
TC1
FULL THREE-PHASE CONNECTION, WITH NEUTRAL
Wiring configuration used for standard applications with full three-phase voltage control
Voltage measurement
Current measurement
Phase angle offset
Capacitor overload measurement
Parameter setting
NOTE: Recommended fuses for aux supply and voltage measurement inputs: F1A (fast).
OUT
1
2
3
4
5
6
7
AUX
SUPPLY
110-250V=
9 10 11
19
12 13 14 15 16 17 18
20 21 22
nc A1 A2
FU10
FU1
R
FU12
FU11
KM1
R
K1
3 ph-to-ph voltage readings
L1-L2, L2-L3, L3-L1
L1-L2-L3 phases
90°
3 readings calculated on L1-L2, L2-L3, L3-L1
P02.03 = Three-phase P02.22 = LV
P02.04 = L1-L2-L3
P02.06 = L1-L2-L3
OUT
1
2
3
4
5
6
7
AUX
SUPPLY
9 10 11
19
12 13 14 15 16 17 18
20 21 22
nc A1 A2
FU10
FU1
R
FU11
FU12
KM1
R
K1
3 ph-to-n and 3 ph-to-ph voltage readings
L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1
L1-L2-L3 phases
3 readings calaculated on L1-L2, L2-L3, L3-L1
P02.03 = Three-phase P02.22 = LV
P02.04 = L1-L2-L3
P02.06 = L1-L2-L3-N
8
FU2
FU8
R
KM2
KM8
R
K2
K8
8
FU2
FU8
R
KM2
KM8
R
K8
K2
G
B
R
Contattori BFK...
BFK... contactors
R
R
Contattori BFK...
BFK... contactors
R
25