Test Failed Screen; Open And Short Fault - AEMC Instruments Wire Mapper Pro CA7028 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.8

Test Failed Screen

4.8.1 Open and Short Fault

In the event of an Open fault, the following is displayed:
Notice the word FAILED under the cable ID1 and also the detailed mes-
sage at the bottom of the display.
The graphical portion of the display also shows that the fault is an open on
pin 7 at the remote end by showing a break in the line at this point.
NOTE: In the event that an open or short circuit fault occurs at
either end of a cable or link under test, the unit will show the fault
as at the near end or the remote end. These faults are the most
common and are mainly due to termination problems.
If the fault occurs some way along the cable or link under test,
then a display similar to the one shown below will occur. Notice,
that on this occasion the actual measured distance to the fault
is given.
In the event of a Short fault, the following is displayed:
In this situation, the graphical portion of the display also shows that the fault
is a short between pins 1 and 2 and the short is drawn at an approximation
to the distance along the cable or link under test, at which it occurs.
Wire Mapper Pro Model CA7028
ID1
4 5 1 2 3 6 7 8 S
FAILED
TIA568
L=94ft
Vp=71%
4 5 1 2 3 6 7 8 S
Open at remote end
Pin 7
ID1
4 5 1 2 3 6 7 8 S
FAILED
TIA568
L=94ft
Vp=71%
4 5 1 2 3 6 7 8 S
Short at 36ft
Pin 1 2