WARNING:
Connection of this 265 V AC product to a branch circuit
MUST be done by direct connection in accordance with
the National Electrical Code. Plugging this unit into a
building mounted exposed receptacle is not permitted
by code.
These models must be installed using the appropriate
GE power supply kit for the branch circuit amperage
and the electrical resistance heater wattage desired.
Use the POWER CONNECTION CHART on page 17
to determine the correct kit required. One of the
following installation methods (A or B) must be used.

HOW TO CONNECT

1 Remove the room cabinet.
2 Connect to electrical power.
3 See the special instructions below for applicable
supply voltages.
4 Reinstall the room cabinet.
A. FOR SUBBASE INSTALLATION
Electrical subbase kits are available to provide a flexible
enclosure for direct connection.
Branch Circuit and
Unit Amperage Rating
15
20
30
The instructions provided with the selected subbase kit must
be carefully followed. It is the responsibility of the installer
to ensure the connection of components is done in
accordance with these instructions and all electrical codes.
B. FOR DIRECT CONNECT
INSTALLATION
If an electrical subbase is not used, direct connection to
branch circuit wiring inside the provided junction box must
be done in accordance with the following steps.
Installation Instructions
265 VOLT ELECTRICAL SUPPLY
Proper GE
Power
Subbase Kit
Supply Kit
RAK204E15
RAK5172
RAK204E20
RAK5202
RAK204E30
RAK5302
REMOVE JUNCTION BOX
1
1 Remove the junction box cover by removing the
front two screws.
2 Remove the junction box by removing the top and
bottom rear screws. Note how the tabs on the lower
left side of the junction box serve to hold the side in
place. This will help when the box is being reinstalled.
CUT AND STRIP THE CORDSET
2
1 Remove the cordset from the power supply kit.
Measure 6" down the cord from where it emerges
from the back of the nylon plastic connector
and cut the cord through at this point.
2 Carefully remove 3" of the cordset insulation
so as to expose the three insulated wires.
3 Strip 3/4" of the insulation away at the end
of each of the three wires (L1, Neutral and
Ground). Plug the connector fully into place
in the unit mating connector. Be sure the
locking tabs at the sides are engaged.
Connector
NOTE: Order Kit RAK4002CW to enable a quick
disconnect inside the junction box.
15
Unit connector
Junction
Junction
box
box cover
3/4"
3"
6"