3-5. UPS Setting
01: Output voltage setting
Interface
02: Frequency Converter enable/disable
Interface
03: Output frequency setting
Interface
INFOSEC UPS SYSTEM – 15 rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
51
Hot Line Tel: +33 (0)2 40 76 15 82 – fax: +33(0)2 40 94 29 51 – hotline@infosec.fr – 04 17 AA 59 205 87
Parameter 2
Parameter 1
Setting
For 208/220/230/240 VAC models, you may choose the following
output voltage:
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac
240: presents output voltage is 240Vac
For 110/150/120/127 VAC models, you may choose the following
output voltage:
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac
127: presents output voltage is 127Vac
Setting
CF ENA: converter mode enable
CF DIS: converter mode disable
Setting
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode enable, you may choose the following output
frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
There are two parameters to set up the
UPS.
Parameter 1: It's for program
alternatives. There are 9 programs to
set up:
Parameter 2: It's for setting
information display。