1. Safety precautions
Before installing the unit, make sure you read all the "Safety precau-
tions".
Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the "Safety precautions," use, and
maintenance of the unit to the customer according to the information in the Operation
Manual and perform the test run to ensure normal operation. Both the Installation
Manual and Operation Manual must be given to the user for keeping. These manuals
must be passed on to subsequent users.
Warning:
The user should never attempt to repair the unit or transfer it to another location.
Use only specified cables for wiring. The wiring connections must be made
securely with no tension applied on the terminal connections. Also, never
splice the cables for wiring (unless otherwise indicated in this document).
Failure to observe these instructions may result in overheating or a fire.
an authorized technician to install them.
Have all electric work done by a licensed electrician according to local regulations.
The appliance shall be installed in accordance with national wiring regulations.
Caution:
to coat flares and flange connections.
or artwork are kept.
2. Installing the indoor unit
1
3
5
2
4
6
4. Electrical work ...........................................................................................6
6. Test run ....................................................................................................17
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts.
: Indicates that the main switch must be turned off before servicing.
: Beware of electric shock.
: Beware of hot surface.
: At servicing, please shut down the power supply for both the Indoor and
Outdoor Unit.
Warning:
Install the indoor unit at least 2.4 m (8 ft) above floor or grade level.
For appliances not accessible to the general public.
service agent or similarly qualified persons in order to avoid a hazard.
the refrigerant should leak.
requested to wear protective equipment such as gloves, etc.
any other refrigerant and do not allow air to remain in the lines.
The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
perature/high humidity (dew point above 26 °C, 79 °F), dew condensation may
be produced in the indoor unit or the ceiling materials. When operating the
units in this condition, add insulation material (10 to 20 mm, 13/32 to 15/32
inch) to the entire surface of the unit and ceiling materials to avoid dew con-
densation.
2.1. Check the indoor unit accessories (Fig. 2-1)
The indoor unit should be supplied with the following accessories.
Accessory name
1
Installation template
Washers (with insulation)
2
Washers (without insulation)
Pipe cover (for refrigerant piping joint)
3
small diameter (liquid)
large diameter (gas)
Band (large)
4
Band (middle)
Band (small) * Use only one.
5
Drain socket
6
Insulation
-
Q'ty
1
4
4
1
1
6
2
2
1
1