3
Technical specifications
3.1
Approvals, tests and conformities
FloCo-Top-1K
Table 4: Technical specifications
Parameter
General specifications
Dimensions (W x H x D)
Burner connection
Tank connection
Nozzle capacity
Return flow
Separating capacity air/gas,
depending on air content of
fuel
Mounting position
Operating overpressure
Suction vacuum
Test pressure
Filter insert:
Materials
De-aerator hood
Filter cup
Housing
Operating temperature range
Ambient
Medium
FloCo-Top-1K is TÜV-tested, report no. S 133 2013 E2.
– English –
Value
165 x 221 x 98 mm
G 3/8 male with 60° cone for burner
hose
G 3/8 female at shut-off valve
Max. 100 l/h
Max. 120 l/h
> 4 l/h (de-aeration unit only)
> 6 l/h (as per EN 12514-3)
Float housing vertical to the top
Max. 0.7 bar (corresponds to a static
oil column of approx. 8 m)
Max. 0.5 bar
6 bar
40 µm, sintered plastic
Transparent plastic
Transparent plastic
Zinc die cast
Max. 60 °C
Max. 60 °C
Technical specifications