MENU
ENTER
MIFIIN
MAIN SETTINGS
ESC
ENTER
MAIN SETTINGS
GROUND TOC 51G
ESC
ENTER
MAIN SETTINGS
PHASE IOC 50G1
ESC
ENTER
ESC
GEK-106619C
Trip enable 51G
Pickup 51G
Curve 51G
TD mult 51G
Def time 51G
Trip enable 50G1
Pickup 50G1
Delay 50G1 [0,00] – 600.00
MAIN SETTINGS
GROUND IOC 50G2
MAIN SETTINGS
THERMAL MODEL 49
Trip enable 49
Pickup 49
Alarm level 49
Heat time 49
Cool time 49
MIFII-N Protección Digital de Alimentador Monofásica
TECLADO Y DISPLAY
- yes – [No]
0,10 – 2,40 [0.50]
[DEFINITE TIME]-USER-MOD INVERSE-VERY INVERSE-
EXTR INVERSE – INVERSE SHORT – INVERSE LONG
0.05 – 2.00 [0.50] (IEC)
0.5 – 20.0 [5.00] (ANSI)
0.5 – 10.0 [0.50] (IAC)
0.00 – 600.00 [5.00] (ANSI)
- Yes – [No]
0,10 – 30,0 [1.0]
Yes
[No]
0.10 – 2.4 [1.00]
70 – 100 [80]
3 – 600 [6]
[1] - 6
8-7