ENGLISH

SSW06 QUICK INSTALLATION GUIDE

SAFETY NOTICES

DANGER!
Only qualified personnel should plan or implement the
installation, start-up, operation and maintenance of this
equipment.
These personnel must follow all safety instructions
included in the manuals of the product and/or defined by
local regulations.
Failure to comply with these instructions may result in
personal injury and/or equipment damage.
NOTE!
In this guide, qualified personnel are defined as people
that are trained to:
Install, ground, power-up and operate the SSW06
ƒ
according to the manuals of the product and the
local required safety procedures.
Use of safety equipment according to the local
ƒ
regulations.
Administer First Aid Treatment.
ƒ
DANGER!
Always disconnect the main power supply before
touching any electrical component associated with the
SSW06.
High voltages and spinning parts (fans) may be present
even after switching off the power supply. Wait at least
3minutes for the complete discharge of the capacitors
and until the fans stopped.
Always connect the equipment frame to the protection
earth (PE) in the appropriate place for this.
ATTENTION!
All electronic boards have components that are sensitive
to electrostatic discharges. Never touch any of the
electrical components or connectors.
If necessary to do so, touch the properly grounded
metallic frame or use a suitable ground strap.
DANGER!
Do not apply a high voltage (High Pot) test on the
SSW06! If this test is necessary, contact the
manufacturer.

RECEIVING AND STORAGE

When receiving the product verifies if:
The SSW06 nameplate data matches the purchase order;
ƒ
The equipment has not been damaged during transportation. If
ƒ
any problem is detected, contact the carrier immediately.
If the SSW06 is not to be installed immediately, store it within
ƒ
its original cardboard box in a clean and dry room (Storage
temperatures between -25°C (-13°F) and 65°C (149°F).

MECHANICAL INSTALLATION

The SSW06 must be mounted in a free environment of:
Direct exposure to sunlight, rain, excessive moisture or marine
ƒ
environment;
SSW06 Installation Guide
Explosive or corrosive gases and liquids;
ƒ
Excessive vibration, dust or metallic and/or oil particles in the air.
ƒ
Allowed Environment Conditions:
Temperature: 0ºC to 55ºC (32ºF to 131ºF) – models 10A to 820A;
ƒ
0ºC to 40ºC (32ºF to 104ºF) – models 950A to 1400A.
Relative Air Moisture: 5%to 90%, non-condensing.
ƒ
Degree of Pollution: 2 (according to UL508).
ƒ
More details to see User´s Guide – Chapter 3 - Item 3.1.1 -
Environment Conditions.
Positioning and Fixing:
Free spaces for cooling air flow must be left open around the SSW06,
as shown.
A
Model
mm(in)
SSW06.0010
150
to
(5,90)
SSW06.0950
SSW06.1100
150
and
(5,90)
SSW06.1400
Install the SSW06 on a flat surface.
ƒ
Do not place heat sensitive components above the SSW06.
ƒ
ATTENTION!
Foresee independent conduits or electroducts for
physically separating the signal, control and power
conductors
Provide at least a 0.25m (10 in) space between sensitive
equipment and wiring from the SSW06, and the cables
between the SSW06 and the motor.
B
C
Y
mm(in)
mm(in)
mm(in)
150
30 (1,18)
50 (1,96)
(5,90)
100
150
50 (1,96)
(3,93)
(5,90)
Page 5