Base Pan Heater; Alternative Outdoor Sensor; Bivalent Connection - Panasonic ADC0916H9E8 Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 455

6. Base pan heater

Select whether Base pan heater is installed or not.
If set Yes, select to use either heater A or B.
A: Turn on Heater when heating with defrost operation only
B: Turn on Heater at heating

7. Alternative outdoor sensor

Set Yes if outdoor sensor is installed.
Controlled by optional outdoor sensor without reading the outdoor sensor of heat
pump unit.

8. Bivalent connection

Set if heat pump linked with boiler operation.
Connect the start signal of the boiler in boiler contact terminal (main PCB).
Set Bivalent connection to YES.
After that, please begin setting according to remote controller instruction.
Boiler icon will be displayed on remote controller top screen.
There are 3 different modes in the boiler operation. Movement of each modes are shown below.
1 Alternative (switch to boiler operation when drops below setting temperature)
2 Parallel (allow boiler operation when drops below setting temperature)
3 Advanced Parallel (able to slightly delay boiler operation time of parallel operation)
When the boiler operation is "ON", "boiler contact" is "ON", "_"(underscore) will be displayed below the boiler icon.
Please set target temperature of boiler to be the same as heat pump temperature.
When boiler temperature is higher than heat pump temperature, zone temperature cannot be achieved if mixing valve is not installed.
This product only allows one signal to control the boiler operation. Operation setting of boiler shall be responsible by installer.
Alternative mode
operate boiler only
-10°C (setting from remote controller)
Advanced Parallel mode
For heating
operate boiler and heat
pump simultaneously
-10°C (setting from remote controller)
Although heat pump operates
but water temperature does
not reach this temperature for
more than 30 mins (setting
from remote controller)
Boiler temp. ON
Boiler temp. OFF
= Setting -8°C
= Setting -2°C
(setting from
(setting from
remote controller)
remote controller)
In Advanced Parallel mode, setting for both heating and tank can
be made simultaneously. During operation of "Heating/Tank" mode,
when each time the mode is switched, the boiler output will be
reset to OFF. Please have good understanding on the boiler control
characteristic in order to select the optimal setting for the system.
24
ACXF60-04180_EN ES IT.indb 24
ACXF60-04180_EN ES IT.indb 24
Initial setting: No
Initial setting: No
Initial setting: No
operate heat pump only
Outdoor temp.
operate heat pump only
Outdoor temp.
AND
Circulation water temp.
Setting temp
System setup
Tank connection
Buffer tank connection
Tank heater
Base pan heater
Select
System setup
Buffer tank connection
Tank heater
Base pan heater
Alternative outdoor sensor
Select
System setup
Tank heater
Base pan heater
Alternative outdoor sensor
Bivalent connection
Select
Parallel mode
operate boiler and heat
operate heat pump only
pump simultaneously
-10°C (setting from remote controller)
For DHW tank
operate boiler and heat
pump simultaneously
-10°C (setting from remote controller)
AND
If actual tank temp. does
not achieve the setting
temp. within 30min
Tank temp.
Heat pump
(setting from remote
Lowering
thermo ON
controller), the boiler
Tank
Boiling initial
temp.
temp.
Heat
30 min (setting from
pump
remote control)
Boiler
17:26, Wed
Confi rm
17:26, Wed
Confi rm
17:26, Wed
Confi rm
Outdoor temp.
operate heat pump only
Outdoor temp.
When tank
temp. is
achieved, both
operations
stop
turn ON
Tank setting
temp.
time
11/17/2016 9:12:40 AM
11/17/2016 9:12:40 AM

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Wh-adc1216h6e5

Tabla de contenido