Theory of Operation
The TM-1100 series of Room Command Modules are designed for use with the TC-9102/9 and AD-TCU series of DDC
terminal unit controllers. The set point dial enables the room occupant to adjust the working set point of the controller within the
range of 12 to 28 °C or +/- 3°C, according to the model number.
The occupancy button enables the occupant to change the mode of operation of the controller from "COMFORT" (occupied) to
"STANDBY" or to request a temporary "COMFORT" (bypass) mode during "NIGHT" (unoccupied) operation.
The current operating mode is shown by an LED indicator. For Fan Coil Unit controllers, a Room Command with a three-speed
fan override adjuster is available, and models without a temperature sensor are provided for application where the room tem-
perature sensor is mounted inside the Fan Coil Unit.
CE Compliance
Directive 89/336/EEC, EN-61000-6-3, EN-61000-6-2
Tools Needed
flat-head screwdrivers (3mm and 5 mm)
drill, bits, and appropriate 4mm screws and plugs
pointed tool (available from Johnson Controls, Ordering CodeTM-9100-8900)
Dimensions
Size: 80 mm x 80 mm x 35 mm
Weight: 0.15 kg
Environmental Data
Ambient Operating Conditions: 0 to +50 °C
Ambient Storage Conditions: -20 to +70 °C
Housing Material: ABS + PC, self-extinguishing HB UL94.
Housing Protection: IP30 (EN 60529)
Temperature Sensor: NTC Thermistor 0 to 40 °C , 2252 ohm at 25 °C.
Remote Set Point: 10 kOhm potentiometer marked for
Series Room Command Module
10 to 90% RH non condensing
10 to 90% RH non condensing
Supply Voltage: Power from TC-9102/9 or AD-TCU Series Controller
12 to 28 °C or +/- 3°C
This document is subject to change without notice
Installation instructions
TM-1100
1
P/N 24-85731-52 Rev A
Issue Date: 03 2005

Publicidad