Overview
8. Electrical connection
Refer to the electrical wiring diagram on the next to last page.
The water heater can only be turned on after it has been filled with water.
The water heater must be permanently powered by electricity.
The water heater can only be connected and operated on a single-phase 230V AC grid. Connect the water
heater using a rigid cable with 1.5 mm² conductors. The installation will include:
• An omnipolar 16A circuit breaker with a contact opening of at least 3mm,
• Protection by a 30mA differential circuit breaker.
If the power cable is damaged, it must be replaced by the manufacturer, their after sales service or a similarly
qualified person, in order to avoid any danger.
Never power the heating element directly.
The safety thermostat fitted to the electric heater must under no circumstances be repaired by anyone other
than our service staff. Non-compliance with this clause will void your warranty.
The appliance must be installed in accordance with the national regulations concerning electrical
installations.
Electrical connection diagram
The ground connection is mandatory.
Installation
16A
Use
Maintenance
3 x 1,5mm²
m²
Warranty
EN