5: Test Function
Test the function of the UPS system by either pressing the On-Switch "I" or disconnecting the input of the UPS system
from the power supply..
6: Turn Off the UPS
6.1. In Inverter Mode:
Press OFF button continuously for more than 1 second to turn off the UPS. Then the UPS will get into self-test status first.
After having finished the self-test, the UPS will get into bypass mode and the Utility Power LED and Bypass LED will light
up. At this time, the UPS might has output. Disconnect the utility power to turn off the output..
6.2. In Battery Mode:
Press OFF button continuously for more than 1 second to turn off the UPS. Then the UPS will get into self-test status first.
After having finished the self-test, the UPS will be turned off completely.
7: Audible Alarm Mute Function
If the alarm is too annoying in battery mode, you may press "I" button continuously for more than 1 second to clear it.
Moreover, the alarm will be enabled when the battery is low to remind you to shutdown the load soon.
8: Operation Procedure of External Battery for Long Backup time Model ("S" Model)
8.1. Use the battery pack with voltage: 36VDC for 1KS (3 pcs of 12V batteries), 96VDC for 2KS/ 3KS (8 pcs of 12V
batteries). Connection of batteries more than or less than required will cause abnormality
8.2. One end of the external battery cord is a plug for connecting the UPS and the other end has a plug for connecting the
user battery cabinet.
8.3. Do not connect the UPS to any load yet. Then, connect the power cord of the UPS to supply utility power to the UPS
to make the UPS operate in utility power mode.
8.4. Connect the plug of the external battery cord to the external battery socket on the rear panel of the UPS to complete
the connection procedure and the UPS will start to charge the battery pack.