Usb 3G/4G Modem (Dongle) Settings; Installation; Installation Of The Ethernet Cable And Grounding; Silicon Plug Installation (Ensure Seals) - WEG Cassia X1000 Manual Del Propietário

Ocultar thumbs Ver también para Cassia X1000:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

www.weg.net
Security mode
None
WPA2-PSK
WPA [TKIP]+WPA2 [AES]
EAP
PEAP-
MSCHAPV2
[Enterprise] WPA2
[Enterprise] WPA [TKIP]+
WPA2 [AES]
TTLS
TLS
ID, password and CA certificate, Private Key and Password

5.4.5 USB 3G/4G modem (dongle) settings

a) Before using the 3G/4G USB modem, make sure it is working and provides Internet access using a
computer.
b) Plug the modem into the USB port at the bottom of the gateway and select the correct model via the "USB
Dongle Type" tab. Set the parameters if necessary.
Figure 5.9 - USB 3G/4G modem (dongle) settings
c) Modems with RNDIS Driver Ethernet Type 1 and Type 2 are supported:
Type 1: an APN must be specified. For example, wyleslte.gw7.vzwentp and 10569.mcs is KORE Wireless
APN. NOTE: If a SIM card from another provider is used, you should ask such provider about the
correct APN to be used.
Type 2: Setup occurs automatically, thus presenting the LAN network. For example, the Huawei E3372s-153
modem.
30
Gateway X1000
Required data
---
Password
Necessary
[Enterprise] WPA [TKIP] + WPA2 [AES]
ID and password
ID, password and CA certificate

6. INSTALLATION

DANGER!
Risk of electric shock. Do not touch electrically energized parts or devices. Before starting to install the
gateway, disconnect the power supply.
ATTENTION!
Acceptable environmental operating conditions: temperature from -40 °C up to 65 °C (rated conditions).
The gateway installation in the field is simple and does not require the use of advanced tools. The signal range
depends on factors such as physical barriers between the gateway and sensors, signal interference and proper
installation. It is estimated that the signal range in industrial environments can reach 30 meters and in the open
field (without interference or barriers) 50 meters.

6.1. INSTALLATION OF THE ETHERNET CABLE AND GROUNDING

( 1 ) Remove the bottom cover.
( 2 ) Insert the Ethernet cable into the proper port
and install the grounding in the marked position.
Reinstall the bottom cover.
Figure 6.1 - Installation of the Ethernet cable and grounding

6.2. SILICON PLUG INSTALLATION (ENSURE SEALS)

Figure 6.2 - Silicon plug installation (ensure seals)

6.3. INSTALLATION IN THE OPERATING ENVIRONMENT

(1) Install the mounting bracket using the screws and bushings (when wall mounted) or the metal clamps (when
mounted on posts).
(2) Fix the gateway to the bracket by pushing it until it clicks into position.
(3) The direction for the best signal reception is located on the Cassia logo. It is recommended to install it in an
environment without obstructions between the gateway and the sensors, away from the floor.
Figure 6.3 - Installation in the operating environment
www.weg.net
(1) Install the silicone plug on the
Ethernet cable.
(2) Slide the plug into the opening
at the bottom base.
(3) Install the 3 plugs into the bottom holes.
Gateway X1000
31

Publicidad

Tabla de contenido
loading

Tabla de contenido