SOMFY FREEROLL RTS Manual De Instalación página 16

Ocultar thumbs Ver también para FREEROLL RTS:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Two types of connections can be made:
Standard (without self test)
Necessity to check correct functioning every 6
months
Position of the DIP switches on the cell:
Without self test: DIP switch1 and DIP switch2 on ON
With self test: DIP switch1 on ON and DIP switch2 on OFF
c. Key-switch
Refer to the general electrical diagram page 42, use the T13 – T14
– T15 terminals.
d. Alarm buzzer
Connection to the control unit
The alarm must be wired to the control unit. The red sheathed cable is wired to T10 and the black
sheathed cable is wired to T16.
If a photo-electric cell is also wired to the control unit, the photo-electric cell must be wired in
standard mode (without self-test).
Alarm activation
Warning! The door must be fully open.
To activate the alarm, push and hold the S-E-C button until the amber LED (above the button) goes
from flashing to solid.
The alarm sounds for five minutes if the roller is lifted manually above the BOTTOM Magnet. To reset
the alarm press the button on a remote control. The rolling garage door will start moving in the up
direction.
With self test
Push Switch 1 of the block DIP 1 to the ON
position (PEC self-check software on; cf.
SETTINGS part page 37).
This means that an automatic test is conducted to
check cell operation every time the door operates. If
the test fails, no door movement is possible.
Wire that must be
added
installer
by
the
36

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido