10. MAIN CHARACTERISTICS.
• Supply voltage: 3 V d .c . with 2 AA LR6 1 .5 V batteries (pro-
vided) .
• Battery life: over a year .
• Output: relay with 5(2) A 250 V~ clean change-over contact
• Adjustment type: ON/OFF .
• Displayed temperature update: every 20 s .
• Room temperature display: 0 °C +40 °C .
• Reading resolution: 0 .1 °C .
• Settings resolution: 0 .1 °C
• Reading accuracy:
- ≤ ±0,5 °C between +15 °C and +30 °C;
- ≤ ±0,8 °C at the extremes .
• Temperature differential: adjustable from 0 .1 °C to 1 °C .
• Adjustment range:
- +4 °C - +15 °C on antifreeze;
- +5 °C - +35 °C on heating or air conditioning .
• Clock error: ≤ ±1 s a day .
• Main functions:
34 - ENGLISH
- hourly temperature setting;
- 3 programmable temperature levels for heating + 3 temperature
levels for air conditioning + 1 antifreeze level;
- weekly programming;
- 1 automatic program that can be set by the user (for both heat-
ing and air conditioning);
- possibility of forcing the program by changing the temperature
manually;
- adjustment for heating and air conditioning;
- antifreeze function;
- possibility of turning off with timer;
- turning on with a phone actuator;
- display in degrees Celsius or Fahrenheit;
- device reset .
• Protection rating:
- IP40 with screw against removal included;
- IP20 with screw against removal not included .