5. Trouble Shooting
Having trouble?
Noise is louder than speci cations.
Nothing appears in the wireless remote controller display, the display
is faint, or signals are not received by the indoor unit unless the remote
controller is close.
The operation lamp near the receiver for the wireless remote controller
on the indoor unit is ashing.
Warm air blows from the indoor unit intermittently when heating mode is
off or during fan mode.
Range of application
The range of working temperatures for both the indoor and outdoor units of the series Y, R2, Multi-S is as below.
Caution:
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Mode
Indoor unit
Cooling
15 °C - 24 °C, 59 °F - 75 °F WB
Heating
15 °C - 27 °C, 59 °F - 81 °F DB
Note: As an applicable humidity standard for both indoors and outdoors, we recommend use within a range of 30 - 80% relative humidity.
Warning:
If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refriger-
ant leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors and
comes into contact with the re of a fan heater, space heater, stove, etc., harmful substances will be generated.

6. Speci cations

PLFY-P.NBMU-E2 Series
Model
Power source
Capacity
Cooling <BTU/h>
Heating <BTU/h>
Dimension
Height
Width
Depth
Net weight
Fan Air ow range
DRY
(Low - Middle1 - Middle2 - High)
WET
Noise level (Low - Middle2 - Middle1 - High)
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB, 81 °F DB/19 °C WB, 66 °F WB, Outdoor 35 °C DB, 95 °F DB
Heating: Indoor 20 °C DB, 68 °F DB, Outdoor 7 °C DB, 45 °F DB/6 °C WB, 43 °F WB
*2 This gure ( ) indicates panel's.
10
PUHY
–5 °C - 46 °C, 23 °F - 115 °F DB
–20 °C - 15.5 °C, –4 °F - 60 °F WB
PLFY-P08NBMU-E2 PLFY-P12NBMU-E2 PLFY-P15NBMU-E2 PLFY-P18NBMU-E2 PLFY-P24NBMU-E2 PLFY-P30NBMU-E2 PLFY-P36NBMU-E2
8,000
12,000
9,000
13,500
<inch>
10-3/16 (1-3/8)
<inch>
<inch>
<lbs>
<CFM> 490-530-550-560 490-530-550-560 490-530-550-560 490-530-570-640 560-640-710-780 810-740-640-560 780-880-990-1060
<CFM> 460-500-510-530 460-500-510-530 460-500-510-530 460-490-530-600 530-600-670-740 780-710-600-530 740-850-950-1030
<dB>
27-29-30-31
27-29-30-31
Here is the solution. (Unit is operating normally.)
The indoor operation sound level is affected by the acoustics of the
particular room as shown in the following table and will be higher than
the noise speci cation, which was measured in an echo-free room.
High sound
absorbing rooms
Broadcasting
Location
studio, music
examples
room, etc.
Noise levels
3 to 7 dB
The batteries are low.
Replace the batteries and press the Reset button.
If nothing appears even after the batteries are replaced, make sure
that the batteries are installed in the correct directions (+, –).
The self diagnosis function has operated to protect the air conditioner.
Do not attempt to repair this equipment by yourself.
Turn off the power switch immediately and consult your dealer. Be
sure to provide the dealer with the model name.
When another indoor unit is operating in heating mode, the control
valve opens and closes occasionally to maintain stability in the air
conditioning system. This operation will stop after a while.
* If this will cause an undesirable rise in the room temperature in
small rooms, etc., stop the operation of the indoor unit temporarily.
Outdoor unit
PURY
–5 °C - 46 °C, 23 °F - 115 °F DB
–20 °C - 15.5 °C, 10 °F - 60 °F WB
Single 208/230 V 60 Hz
15,000
18,000
17,000
20,000
33-1/16 (37-3/8)
33-1/16 (37-3/8)
51 (13)
28-29-30-31
28-29-30-32
Low sound
Normal rooms
absorbing rooms
Reception room,
Of ce, hotel
hotel lobby, etc.
room
6 to 10 dB
9 to 13 dB
PUMY
–5 °C - 46 °C, 23 °F - 115 °F DB
–18 °C - 15.5 °C, 0 °F - 60 °F WB
24,000
30,000
36,000
27,000
34,000
40,000
11-3/4 (1-3/8)
60 (13)
28-31-34-37