MZ electronic MZBC 2460 Instrucciones De Uso página 22

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Signals and operational anomalies
PILOT LIGHT
LINE
STATUS
TEMP.BATTERY
TEMP.CHARGER
NO BATTERY
STATUS,
TEMP.BATTERY,
TEMP.CHARGER,
NO BATTERY
MZBC_2460
SIGNAL
Stable
Flashing
Stable
Stable
Stable
Stable
Flashing
flashing
CAUSE
The battery charger is
fed
The battery is in the
absorption phase.
The battery is in the
maintenance phase.
The battery is
overheated (the
distributed current will
be automatically
reduced).
The appliance has
internal overheating: the
distributed current will
be automatically
reduced.
The battery charger
does not detect the
battery when it is turned
on.
First phase (Boost) >
than 9 hours
Internal or external short
circuit
Overload
22
English
SOLUTION
Normal cycle
Normal cycle
Normal cycle
If the battery
temperature remains
high it is probably
damaged and must be
replaced.
The cycle will not be
stopped but its length
will be increased.
Check the battery
connections. If the
battery is connected
check the cell efficiency
with a densimeter.
Turn off the power of
the battery charger and
find the cause of the
short circuit or of the
overload.
Rev. 02– 2015

Publicidad

Tabla de contenido
loading

Productos relacionados para MZ electronic MZBC 2460

Tabla de contenido