Special Functions; System Control (Fig. 9-1) - Mitsubishi Electric Mr.SLIM PUHZ-P200YHA Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 38
8. Special Functions
A
Orange
SW1
A Circuit diagram example (low noise
mode)
B On-site arrangement
A
Orange
SW2
A Circuit diagram example (Demand func-
tion)
B On-site arrangement
8.3. Refrigerant collecting (pump down)
Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.
1 Supply power (circuit breaker).
* When power is supplied, make sure that "CENTRALLY CONTROLLED" is not
displayed on the remote controller. If "CENTRALLY CONTROLLED" is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.
2 After the gas stop valve is closed, set the SWP switch on the control board of
the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor
and outdoor units) start operating and refrigerant collecting operation begins.
LED1 and LED2 on the control board of the outdoor unit are lit.
* Only set the SWP switch (push-button type) to ON if the unit is stopped. How-
ever, even if the unit is stopped and the SWP switch is set to ON less than
three minutes after the compressor stops, the refrigerant collecting operation
cannot be performed. Wait until compressor has been stopped for three min-
utes and then set the SWP switch to ON again.
9. System control (Fig. 9-1)
E SW 1 - 3 ~ 6
ON
OFF
3 4 5 6
ON
F SW 1 - 3 ~ 6
OFF
3 4 5 6
ON
G SW 1 - 3 ~ 6
OFF
3 4 5 6
E
A
F
A
TB1
TB1
TB4
TB4
TB4
B
B
B
2
TB5
TB5
2
1
C
D
1
Fig. 9-1
10
Red
3
Brown
Fig. 8-1
1
CNDM
C External input adapter (PAC-SC36NA)
D Outdoor unit control board
E Max. 10 m
Red
3
Brown
Fig. 8-2
1
CNDM
C External input adapter (PAC-SC36NA)
D Outdoor unit control board
E Max. 10 m
A Outdoor unit
B Indoor unit
C Master remote controller
D Subordinate remote controller
E Standard 1:1 (Refrigerant address = 00)
F Simultaneous twin (Refrigerant address = 01)
G Simultaneous triple (Refrigerant address = 02)
A
G
TB1
TB4
TB4
TB4
B
B
B
TB5
8.1. Low noise mode (on-site modification) (Fig. 8-1)
By performing the following modification, operation noise of the outdoor unit can be
reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on
the control board of the outdoor unit.
• The ability varies according to the outdoor temperature and conditions, etc.
1 Complete the circuit as shown when using the external input adapter
(PAC-SC36NA). (Option)
2 SW1 ON: Low noise mode
SW1 OFF: Normal operation
8.2. Demand function (on-site modification) (Fig. 8-2)
By performing the following modification, energy consumption can be reduced to 0
–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on
the control board of the outdoor unit.
1 Complete the circuit as shown when using the external input adapter
(PAC-SC36NA). (Option)
2 By setting SW7-1 and SW7-2 on the control board of the outdoor unit, the
energy consumption (compared to the normal consumption) can be limited as
shown below.
SW7-1
SW7-2
OFF
OFF
ON
OFF
OFF
ON
3 Because the unit automatically stops in about two to three minutes after the
refrigerant collecting operation (LED1 and LED2 are lit), be sure to quickly
close the gas stop valve. When LED1 and LED2 are lit and the outdoor unit is
stopped, open the liquid stop valve completely, and then repeat step 2 after
three minutes have passed.
* If the refrigerant collecting operation has been completed normally (LED1
and LED2 are lit), the unit will remain stopped until the power supply is turned
off.
4 Turn off the power supply (circuit breaker).
* Note that when the length of the extension piping is long, it may not be pos-
sible to perform a pump-down operation. When performing the pump-down
operation, make sure that the low pressure is lowered to near 0 MPa (gauge).
* Set the refrigerant address using the DIP switch of the outdoor unit.
1 Wiring from the Remote Control
This wire is connected to TB5 (terminal board for remote controller) of the indoor
unit (non-polar).
2 When a Different Refrigerant System Grouping is Used.
Up to 16 refrigerant systems can be controlled as one group using the slim MA re-
mote controller.
Note:
In single refrigerant system (twin/triple), there is no need of wiring 2.
SW1
Function
Function table
1 Compulsory
<SW1>
defrosting
2 Error history
ON
SW1
OFF
clear
function
3
Refrigerant
settings
4
system ad-
5
dress setting
6
Energy consumption (SW2 ON)
0% (Stop)
50%
75%
Operation according to switch setting
ON
OFF
Start
Normal
Clear
Normal
Settings for outdoor unit addresses
0 to 15