Water pump logic:
1. Parameter setting : P3=0 : Water pump is related to compressor's operation to start or stop.
When heat pump turns on, filtration pump will start first and then fan motor and compressor.
Condition
T1≥Tset-0.5 ℃ , last for
Heating
mode
30 minutes
T1≦Tset+0.5 ℃, last
Cooling
mode
for 30 minutes
1 hour later
Filtration pump will
start to run for 5 mins
to detect the water in
temp.
Note: If the water volume of the swimming pool is small, water temp reaches T1≥Tset+1℃ and last for 5
mins, heat pump will stop first and then filtration pump stops, but it will not entry standby mode for 1 hour.
If water temp drops to T1≤Tset-1, heat pump will start again.
2. While P3=1: When the heat pump is on (running or standby), filtration pump will always be on.
NOTE :
Tset = Tseting water temperature
For example : Tset = 28℃ Tseting water temperature in your pool heat pump
Tset-1 = less 1℃ than Tseting temperature
Tset- 1 = 28-1=27℃
Tset+1= more 1℃ than Tseting temperature
Tset+ 1 = 28+1=29℃
Example
T1≥27.5℃, last
for 30 minutes
T1≦28.5℃, last
for 30 minutes
Example
Condition
Tset=28℃
T1>Tset-1℃ T1>27℃
T1≤Tset-1℃ T1≤27℃
T1<Tset+1℃ T1<29℃
T1≥Tset+1℃ T1≥29℃
Water pump working logic
Filtration pump will enter standby mode for 1
hours and will not start except after manual
power off and restart. Compressor and fan
motor stops first and filtration pump will
stop after 5 mins.
Water pump working logic
Filtration pump will enter standby mode for
another 1 hours and will not start except after
turning off the hp and restart.
Heat pump will start again until it meets the
condition of standby.
Filtration pump will enter standby mode for
another 1 hours and will not start except after
turning off the hp and restart.
Heat pump will start again until it meets the
condition of standby.