CHART 1 - PIPE SIZING
Pump
Pump Model
Opening
Deep Well
Inlet: Suction
Inlet: Drive
Outlet
PRIME PLUG
PRESSURE SWITCH
Figure 5 - Horizontal Tank
AIR VOLUME CONTROL
PRIMING PLUG
OUTLET
Figure 6 - Vertical Tank
Horizontal Distance
(Feet)
0-25
26-100
1-1/4 in.
1-1/2 in.
1 in.
1-1/4 in.
3/4 in.
1 in.
OUTLET
TO JET
AIR
VOLUME
CONTROL
TUBING
AIR
VOLUME
CONTROL
AIR VOLUME
CONTROL
TUBING
SUCTION
DRIVE
DEEP WELL PUMP WITH HORIZONTAL AND VERTICAL STORAGE
TANK (FIGURES 5 AND 6)
1.
Install the air volume control on the tank as shown.
2.
Connect the copper tube from the air volume control to the 1/8 in.
NPT opening directly above the 1-1/4 in. opening on the front of the
pump.
3.
Install a valve and isolating hose between the system and the house
plumbing to aid in pump removal for servicing and for reducing noise
transmitted through the house piping.
4.
Provide a hose bib (faucet) at the lowest point in the system to drain
for service or storage.
DEEP WELL PUMP WITH PRE-CHARGED STORAGE TANK (FIGURE 7)
1.
Check tank pre-charge using a tire pressure gauge. Set air pressure
in tank to 28 psi which is 2 psi below pressure switch cut-in level. An
air valve is located on the side and will accept a standard fitting from
a bicycle pump or air line.
2.
Check the pressure with the power off, faucets open and no water
flowing (zero water pressure).
3.
Install a valve and isolator hose between the system and the house
plumbing to aid in pump removal for servicing and for reducing noise
transmitted to the house through the piping.
4.
Provide a hose bib (faucet) at the lowest point in the system to drain
for service or storage.
OUTLET
PRESSURE
SWITCH
Figure 7 - Pre-charged Storage Tank
5
CWS Series
PRIME PLUG
TO JET
www.waynepumps.com