ABB TF96 Manual De Instrucciones página 8

Ocultar thumbs Ver también para TF96:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 11
Notes
For explosion-proof applications, the efficiency of the installed protection devices has to be verified prior to
commissioning!
The protection function of the device is the thermal overload protection of motors. In case of an overload trip, the motor
is switched off by opening the NC contact of the electromechanical overload relay.
The safe state is an open NC contact of the device used to control the load contactor.
Mounting and commissioning
The TF96 may only be replaced by an equivalent device, marked in accordance with the regulations.
For applications protecting motors in potentially explosive areas, the device may only be used if it is configured for
"manual reset".
Setting the rated motor current is done using the adjusting knob on the front side.
For this purpose, the rated motor current has to be adjusted on the TF96 according to the EC type examination
certificate specification and/or the type plate.
When selecting the overload relay, check its suitability by means of the trip curves and/or the trip class. Decisive values are the
ratio between the motor startup current I
to be marked in the ATEX certificate of conformity or in the EC type examination certificate and on the type plate of the motor.
The thermal overload relay must trip within the time t
coordination point I
/I
and the time t
A
N
The connecting cables have to be dimensioned according to the specifications and/or the applicable standards.
Safety specifications TF96
According to DIN EN 50495, the requirements for a SIL 1 and a HFT = 0 can be placed on safety equipment for categories 2G
and 2D.
The TF96 thermal overload relay can meet these requirements if used as a component of the safety equipment, e.g. in
cooperation with a suitable load contactor.
8 - ATEX TF96
|
and the rated motor current I
A
. This means that the trip curve from the cold state has to be below the
E
.
E
, as well as the shortest time t
N
. These values have
E
2CDC106086M6801b / 04.2016

Publicidad

Tabla de contenido
loading

Tabla de contenido