PRECISE DETECTION OF WATER INSUFFICIENCY (DIAGRAM C)
In the DIGIPRESS model simply introduce the nominal pump current to activate the protection for overcurrent and
insufficient water (see STARTING point 2).
However, it is possible to improve the detection precision for insufficient water activating ADVANCED
PROGRAMMING MENU, the dr1 parameter, proceeding as follows:
• Firstly check, when the system
is without water, that the hydro-
pneumatic tank is inflated at the
required pressure. Then when
the system is loaded, or at the P
stop pressure:
• Enter the ADVANCED
PROGRAMMING MENU
When replacing with a new pump it will be necessary to repeat the process.
Having accessed the current menu by pressing
introduced nominal current predominates.
PRESSURE SENSOR CALIBRATION
In the case of misreading by the sensor, recalibration is possible.
For calibration of the sensor it is necessary to have a pressure gauge installed.
Steps to follow:
PRESSURE CALIBRATION = 0
1. Open the valves to obtain
depressurised installation.
FULL SCALE
1. Start the pump until the
pressure switch cutting
pressure.
COD
DESCRIPTION
O
INSUFFICIENT
A01
( ( O ) )
O
INSUFFICIENT
WATER (FOR
A11
MINIMUM
PRESSURE)
O
A02
OVERCURRENT
( ( O ) )
(((O)))
EXCESSIVE
A04
CYCLES
O
TRANSDUCER
A05
• Press
• Press
and to go to the next one until
reaching dr0.
• Via the key
• Press
learning function of the device
2. Press simultaneously the
buttons and until the screen
2. Press the buttons and
simultaneously until the screen
flashes.
SYSTEM REACTION
With detection of insufficient water shut the device stops.
Restart operation by pressing
With detection of insufficient water with the Automatic Reset system(ART) enabled, a first att-
WATER
empt at 5 minutes is made and afterwards an attempt every 30 minutes during 24 hours. This
alarm can also be reset manually with the button
there is a definitive absence of water
It appears if in normal operation the pressure is below minimum pressure (Px. x) previously set
during the time
(txx) pre-set in the ADVANCED MENU. If the pressure exceeds the minimum pressure, the ope-
ration is automatically reset and the alarm disappears. Normal operation can also be restored
manually by pressing
The overcurrent alarm is activated if the nominal current of the pump is exceeded. The device
performs 4 automated attempts at reset before entering definitive alarm. Normal operation
can also be re-established manually b pressing
Only if activated in the ADVANCED MENU the alarm is generated after three consecutive cyc-
les in a time range less than that set. If rc1 is reactivated, the device does not stop and5 delay
seconds are added for start to protect
the electric pump. If rc2 is activated, the electric pump is stopped. \To end the display on the
alarms screen press
Contact the supplier
FAULT
+
for 5 seconds.
7 times to validate
modify dr1.
to access the self-
3 times, self-learning reading is invalidated and the manually
.
USE AND MAINTENANCE MANUAL
• Open the utility valves and run
water for approximately 15 sec
and then close them.
• The pump will fill the system and
will stop once the stop pressure
P value already set is reached
(see STARTING point 4).
• DIGIPRESS learns the value of
absorbed pump current.
shows 0.0 flashing.
3. Press to validate.
3. Set the pressure values with the
buttons and to indicate the
desired pressure.
4. Press
to validate.
. If the system still occurs after 24 hours,
.
EN
17