Smoke alarm devices are to be used as the bare minimum
bedrooms, children's rooms and hallways which act as escape routes, and are
to be installed in each case in the middle of the room, on the ceiling only (do not
install on a wall) (Fig. 2). Select the highest installation location with a minimum
distance of 50 cm to surrounding walls, furniture and lamps. Configuration is
optimal
when devices are located in all other rooms as well as staircases. In
RM
washrooms (bathrooms, lavatories etc.), a smoke alarm device is generally not
necessary because the risk of fire is low.
Please note the graphics in this manual and the detailed information available in
the EN14676 standard
apartments and rooms with similar purposes – Installation, use and
maintenance".
Where smoke alarm devices should not be installed
Selecting location
"Smoke alarm devices for use in residential buildings,
Outside (use only in closed rooms)
In rooms in which the alarm could be triggered by
disturbance variables (steam, condensation, "normal"
smoke, vapour, dust, dirt or grease)
Next to an air duct or similar ventilation opening (draughts)
In areas in which the temperature can fall below 0°C or
rise to over 40°C
On unstable surfaces with designs that render them
unsuitable for installation with screw anchors