Other Remarks - S&P BEAS Manual De Instrucciones

Modulo de control electrónico de adaptación de señal
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

To change the factory settings:
For Smin = rotate the Smin trimmer (measure between GND and Smin on the J8 terminal block and multiply the
obtained value by 2; e.g. if the reading = 2 V this means Smin is really 4 V).
For Smax = rotate the Smax trimmer (measure between GND and Smax ).
Note:
To make it easier to adjust the aeraulic settings of the installation, the analogical output can be forced using
switches S1.2 and S1.3:
S1.2
OFF
ON
OFF
ON
Logically illegal settings ( = if Emax < Emin or Smax < Smin) cause an LED indicator to flash.
S2.1
OFF
ON
OFF
ON
3.1 Setting the output relay trigger threshold (terminal block J1):
For the relay contact to switch when the analogical input reaches a certain value,
switches S2.1 and S2.2 should be set to ON.
Factory setting: for analogical input = 14.4 mA.
To change the factory settings:
Connect a voltmeter (AC voltage) between GND and Relay on terminal block J8:
Using a flat-headed screwdriver, rotate the trimmer marked " Relay " (e.g. until the voltmeter indicates 2V)
The value matches Relay/4 if analogical input = current
(Example = a reading of 2 V means the relay will trip on an analogical input value of = 2 x 4 = 8 mA)
The reading is Relay/2 if input = voltage
(Example = a reading of 2 V means the relay will trip on an analogical input value of = 2 x 2 = 4 V)

OTHER REMARKS:

Location:
Mount in an equipment room, suspended ceiling or attic.
Dimensions (L x H x D) in mm:
Power supply (J5):
24 V 50 Hz.
Consumption: 1.5 W.
Connection capacity of unpluggable connectors supplied:
For flexible multistrand conductors with end terminals or rigid conductors of section 1 to 2.5 mm².
Electrical properties of built-in relay (J1):
Breaking capacity of contact = 10 A at 250 V AC (cos fi = 0.6) / 16 A at 250 V AC (cos fi = 1).
Output 24 V 50 Hz ( J4 between GND and 24 V):
Output +24 V ( J3 between GND and +24 V):
Output 0-10 V ( J4 between GND and OUT):
electrical insulation rating: 2.
enclosure with
Plastic
IP protection rating:
S1.3
OFF
OFF
ON
ON
S2.2
OFF
OFF
Active output relay with analogical input (J3)
ON
Active output relay with external contact (J7)
ON
Active output relay with analogical input (J3)
175 x 130 x 80.
IP55.
Analogical output
(on connector J4, between GND and OUT )
Automatic (non-adjustable)
Forced to Smax
Forced to Smin
Automatic (non-adjustable)
Output relay
(on connector J1)
Inactive ouput relay
Maximum available current: 100 mA
Maximum available current: 120 mA
Maximum available current: 10 mA

Publicidad