9. ESPECIFICACIONES
Model
VA Rating
Apparent Output Power
Active Output Power
Power Factor
Topology
Type
Agency Approvals
Input
Voltage Window
Frequency
Phase
PF
Typical Transfer Time
AC Leakage current
Surge Protection
Output
Voltage
Voltage Regulation
Frequency(Synchro
nized Range)
Frequency(Battery
Output
Mode)
(INV.
Current
mode)
Factor
Harmonic Distortion
Transient
Response(ms)
Waveform
To AC Mode (Full
load)
Efficiency
To Battery Mode
(Full load)
Battery System
Type
Numbers of Batteries
Backup Time(Full Load)
Recharging Time
Charging Current (Max.)
Charging Voltage
Hot Swappable Battery
Internal battery
DC leakage current
Battery type
Transfer Time
1KVA
1000 VA
800 Watts
230V, adjustable to 200/208/220/230/240
±0.1% (0.05~0.06Hz) unless synchronized to line
Crest
85%
83%
12V/7.2Ah
3
>7min.
1.1A
41.0Vdc±0.5V
≤ 30uA (±10uA) with no AC applied and the unit in the off position
Sealed, non-spillage, maintenance-free, lead acid
2KVA
2000 VA
1600 Watts
0.8
Double conversion On-Line
Rack/Tower
CE
160 – 288 Vac
50/60 Hz auto-select, ± 5Hz
Single phase with ground
>0.99 at full rated linear load
0 ms.
≤ 3.5 mA
300 joules
≤ ± 1% until low battery warning
3Hz or 1Hz (setting by software)
3:1
≦3% THD(Linear Load)
<=60ms/5%
Pure Sine wave
85%
83%
12V/7.2Ah
6
>7min.
4 Hours to 90%
2.16A
82.0Vdc±0.5V
Yes
Yes
3KVA
3000 VA
2400 Watts
88%
85%
12V/9Ah
6
>5min.
2.7A
82.0Vdc±0.5V