safety Manual
14.2.2 If password is set
1
2
3
4
5
6
to
41
Note 8 : open is shown briefly in the display
14.2.3 If any parameter is found to be incorrect during verification
14.3
functional test
the user is responsible to make a functional test after verification of the safety
parameters. the procedure for periodic proof test described in section 10 shall
be used.
in addition, if a process calibration is taken into sil-mode operation (refer to
section 13.3 - advanced functions), it is mandatory that the accuracy of the device
(and sensor, if applicable) are tested.
15 fault reaction and restart condition
When the 9116 detects a fault the outputs will go to safe state, in which the outputs will be
"de-energised".
if the fault is application-specific (cable error detection) the 9116 will restart when the fault
has been corrected.
Power cycle the device for bringing it out of safe state.
20
9116 UNiVeRsal coNVeRteR
action
Press oK
enter password and press oK
set aDV.set to Yes and press oK
set setUP to sil and press oK
set eN.sil to Yes and press oK
(at this time the device starts operating
in sil mode with the entered configuration
parameters!)
as step 6 to 41 for 14.2.1
Remove sil-mode (by entering the password and selecting eN.sil = No).
Go through the setup menu and correct the parameter(s).
Repeat step 1 to 36 (with correct parameters).
Version No. V2R0
Display shows
PassW
aDV.set
setUP
eN.sil
coNFiG
Verify
oPeN->locK
(Note 8 )
as step 6 to 41 for
14.2.1