S&P VFKB 24 Folleto De Instrucciones página 23

Convertidores de frecuencia para motores trifásicos ac
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Rated for 380/460VAC line input only
6.2
GROUND CONNECTION
Connect the ground wire (earth) to the Green Ground Screw. The Ground Screw is located
next to Terminal Block TB1.
6.3
MOTOR CONNECTION
Wire the motor to Terminal Block TB1 Terminals "U", "V", "W". Motor cable length should not
exceed 30 m.
6.4
RUN/FAULT RELAY CONNECTION
The Run/Fault Relay Output Contacts are located at TB2 and can be used to turn on or off
equipment or to signal a warning if the drive is put into the Stop Mode or a fault has occurred.
Power Off
Run Mode
Stop Mode
Fault
7- SETTING SELECTABLE JUMPERS
The drive has customer selectable jumpers which must be set before the drive can be used. All
jumpers have been factory set for most applications.
Disconnect the AC line before changing position of jumpers.
We recommend changing the jumpers indicated in this chapter only and after having read about
their function. An incorrect position of jumpers can destroy the motor.
7.1 LINE INPUT VOLTAGE SELECTION FOR VFKB-24 AND VFKB-27 – JUMPER J1
Jumper J1 is factory installed on Terminal "230V" for 208/230 Volt AC line input. For 115 Volt
AC line input, the jumper must be removed and installed on Terminal "115V".
Description
Main power disconnect.
Normal drive operation
Selected by Operator
Drive Tripped
Run Relay Operation (Jumper J8
Etat
installed in R position)
NO
NC
Open
Closed
Closed
Open
Open
Closed
Open
Closed
Fault Relay Operation (Jumper
J8 installed in R position)
NO
NC
Open
Closed
Closed
Open
Closed
Open
Open
Closed

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Vfkb 27Vfkb 45Vfkb 48

Tabla de contenido