tube banks so that they can be taken out. The tube bank removal can take place through
the sides of the equipment.
MODEL
A (mm)
BA-AF 05
BA-AF 08
BA-AF 18
BA-AF 30
BA-AF 45
BA-AF 56
BA-AF 80
BA-AF 120
5.3. CONNECTING THE EQUIPMENT TO THE WATER SUPPLY
For heat exchangers with threaded connections, tightening is carried out while gripping
the tube bank's manifold with the correct tool so that the stress is not transmitted to the
manifold, thus avoiding damage to the latter.
The following table sets out the type of thread applicable to each battery model:
MODEL
TYPE OF THREAD
BA-AF 05
BA-AF 08
BA-AF 18
BA-AF 30
35x1,5 (1"3/8)
BA-AF 45
42x1,5 (1"5/8)
BA-AF 56
42x1,5 (1"5/8)
BA-AF 80
54x1,5 (2"1/8)
BA-AF 120
54x1,5 (2"1/8)
The water tube banks must operate countercurrent to the flow of air in order to perform
correctly. Accordingly, the fluid inlet must be connected to the manifold located on the
air outlet side and the fluid outlet to the manifold located on the air inlet side as shown in
the diagrams below: