SA SPW-C0705DZH8 Instrucciones De Instalación página 10

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 298
1-5. Tubing Length
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
Balance tubing
(ø9.52)
Explanation of symbols
Distribution joint
(APR: purchased separately)
Ball valve (field supply)
T-joint (field supply)
Solidly welded shut
(pinch weld)
Note: Do not use commercially available T-joints for the liquid tubing
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor
unit connections and tubing branches.
Table 1-2 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Items
Allowable tubing length
Allowable elevation difference
Allowable length of joint tubing
NOT E
1.
The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to the
tube ends.
2.
If the longest tubing length (L1) exceeds 90 m (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for the
discharge tubes, suction tubes, and liquid tubes. (Use a field supply reducer.)
3.
If the longest main tube length (LM) exceeds 50 m, increase the main tube size at the portion before 50 m by 1 rank for the suction
tubes and discharge tubes. (Use a field supply reducer.)
(For the portion that exceeds 50 m, set based on the main tube sizes (LA) listed in the table on the following page.)
1.
2.
3. The outdoor connection main tubing (LO portion) is determined by the total capacity of the
outdoor units that are connected to the tube ends.
4.
Max. 40 cm
Max. 40 cm
Marks
L1
Max. tubing length
Difference between max. length and min. length from the No. 1
∆L (L2 – L4)
distribution joint
LM
Max. length of main tubing (at max. diameter)
Max. length of each distribution tube
1 , 2... 40
Total max. tubing length including length of each distribution tube (only
L1+ 1+ 2... 39+
liquid tubing)
A+ B+LF+LG+LH
L5
Distance between outdoor units
When outdoor unit is installed higher than indoor unit
H1
When outdoor unit is installed lower than indoor unit
H2
Max. difference between indoor units
H3
Max. difference between outdoor units
T-joint tubing (field-supply); Max. tubing length between the first T-joint
L3
and solidly welded-shut end point
Main tubing length LM = LA + LB ... ≤ 80 m
Main distribution tubes LC – LH are selected according to the capacity after the
distribution joint.
Sizes of indoor unit connection tubing 1 – 40 are determined by the connection
tubing sizes on the indoor units.
For
extension
For
extension
and
parts.
Contents
Actual length
Equivalent length
8
T-joint tubing
(header joint system)
Solenoid valve kit
R410A distribution joint
APR-CHRZP680BGB (for outdoor unit)
APR-CHRZP1350BGB (for outdoor unit)
APR-RZP224BGB (for indoor unit)
APR-RZP680BGB (for indoor unit)
APR-RZP1350BGB (for indoor unit)
L = Length, H = Height
Length (m)
≤ 150
≤ 175
≤ 40
≤ 80
*3
≤ 30
≤ 300
≤ 10
≤ 50
≤ 40
≤ 15
≤ 4
≤ 2

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Spw-c0905dzh8Spw-c1155dzh8Spw-c1305dzh8Spw-c1405dzh8

Tabla de contenido