The three-phase adapter box converts the outputs of 5A
into a 1 V
voltage. The three circuits are independent and isolated between the
ac
inputs and the outputs.
For three-phase measurements, start by marking the plugs with the coloured
rings supplied with the power and energy analyser. A different colour for each
plug associated with a current terminal.
Create a short-circuit between the outputs of the secondary of each current
transformer.
L1
Connect each secondary of the current transformer to the input of the 5A adapter
box, taking care with the phase order (L1, L2, L3) and the direction (black ter-
minal to earth).
Warning: Never open the secondary of a current transformer if there is a current
in the primary circuit.
Remove the short-circuits from the outputs of the secondary of the current
transformers.
2. USE
L2
13
current transformers
ac
L3